1 8 ON Program
2 7 OFF Battery 10ºC
3 6 ON Kick up
4 5 ON Stop >25ºC
Default configuration PIV
DANGER, MAINS VOLTAGE!
Make sure you wear hand
protection before handling
connectors (4 and 7)
5
8
7
2
1
3
4
6
1. Time elapsed button
2. Time elapsed display
3. Functions legend
4. Function jumpers
5. Speed button
6. LED speed indicator
7. Voltage
8. LED temperature indicator
Functions
– Certain functions may be modified on the board
through the CN4 jumpers:
Jumper 1-8 = Program.
DO NOT TOUCH
. (On by default)
Jumper 2-7 = Activation temperature for battery.
On - 15ºC. Off - 10ºC (default).
Jumper 3-6 = Kick-up air flow 10% if T > 19ºC.
On – Kick up (default). Off – no kick up
Jumper 4-5 = Stop if T > 25ºC.
On - stop (default for PIV).
Off – non-stop (default for PIV W).
Time counter
- counts the number of hours in use up to 11 years.
Hold the button down to see all the numbers from largest to
smallest.
Speed options
- 4 settings: Trickle, Medium, Large and Boost,
indicated by LEDs: green, yellow, orange and red.
Temperature display-
regardless of the chosen configuration, the air supply temperature is
shown on 3 LEDs: T <19ºC (yellow), >19ºC (orange), >25ºC (red). If the temperature is on the
limit, the LEDs may flash.
Access-
To access the board, remove the two screws from the circular plastic cover. For the PIV W
model, you must detach the duct and remove the exterior housing.
ANNEX
CIRCUIT BOARD
1 8 ON Program
2 7 OFF Battery 10ºC
3 6 ON Kick up
4 5 OFF Stop >25ºC
Default configuration PIV W
Products:
PIV, PIV BP and PIV W