Digital input:
-
NC:
Normally closed contact. The fan will pass to night mode when
DIGITAL INPUT
< (NC) OK
DIGITAL INPUT
< (NO) OK
OK
OK
Digital input:
- NC:
Normally closed contact. The fan will pass to night mode when contact is opened.
- NO:
Normally open contact. The fan will pass to night mode when contact is closed.
OUTPUT PULSES
< 4 OK
Press
or
to manually modify parameter that
displays the speed by J8 output (TACOM).
It is advised
not to modify.
PROGRAM C:1?
< NO YES
Save parameters modified
Program OK
<Pulsar tecla
>
Press any key to return to main screen
OK
OK
OK
OK
SI
SI
6.6.4. Operation PROPORTIONAL/VAV mode
In this mode the control box is ready to work with one or two analog inputs (4-20mA or 0-10V). The control box works according
to the parameter of maximum demand. Sensors are connected to the analog inputs J5 and/or J6.
Operation PROPORTIONAL/VAV mode
Once changed the operation mode to PROPORTIONAL/VAV, following parameters will appear: