MOTOR TYPE
< EC OK
No modify
OK
OK
SENSOR
< INTERNAL OK
SENSOR
<IN1 0-10V OK
SENSOR
<IN1 4-20mA OK
SENSOR
<IN2 0-10V OK
SENSOR
<IN2 4-20mA OK
OK
OK
Sensor: Sensor type
-
INTERNAL:
Pressure differential internal sensor
- IN1 0-10V:
External sensor with analog signal 0-10V (J5 terminal)
- IN1 4-20mA:
External sensor with analog signal 4-20mA (J5 terminal)
- IN2 0-10V:
External sensor with analog signal 0-10V (J6 terminal)
- IN2 4-20mA:
External sensor with analog signal 4-20mA (J6 terminal)
RANGE
< 400Pa OK
Pulsar
o
para modificar manualmente el
parámetro. El valor que aparece en pantalla corresponde
a la escala del sensor interno preajustado en fábrica. Si se
instala un sensor externo, introducir el rango de escala
correspondiente.
SET POINT
< INTERNAL OK
SET POINT
<CONSOLE OK
SET POINT
<IN1 0-10V OK
SET POINT
<IN1 4-20mA OK
SET POINT
<IN2 0-10V OK
SET POINT
<IN2 4-20mA OK
OK
OK
OK
OK
Set Point:
-
INTERNAL:
Factory set value
-
CONSOLE:
Value set by PROSYS ECOWATT console
- IN1/IN2 0-10V:
Value set by external potentiometer (0-10V)
- IN1/IN2 4-20mA:
Value set by external potentiometer (4-20mA)