6. INSTALLATION
6.1. INTRODUCTION
Horizontal models size 04, 08, 12, 16, 21, 27 and 33
These models are designed to be installed hanging from the ceiling or located behind a false ceiling.
When installing the unit, is mandatory to distribute the unit weight between all the supports existing in
the units:
• CADB-HE 04: 4 supports (one in each corner)
• CADB/T-HE 08 to 33: 6 supports (one in each corner and 2 centered in each side)
Using studded rods (Ø 8 mm), it can be secured to the ceiling and levelled.
BdYZa%)
BdYZah%-id((
B
C
A
A
Ø 12
Model
A
B
C
4
-
1558
798
8
894
1788
948
12
869
1738
1088
16
994
1988
1278
21
1169
2338
1678
27
1169
2338
1678
33
1169
2338
1678
The model 04 does not have central support
The installer must ensure that the ceiling structure and the securing elements can bear the weight of
the device, taking into account that it is a dynamic load.
To prevent the transmission of vibrations from the unit to the rest of the installation, it is necessary
that the installer use specifi c isolation elements, such as antivibration devices in the supports, fl exible
sleeves between the unit and the ducts, and fl exible couplings between the water connections and the
pipelines.
Model
Weight (kg)
4
147
8
183
12
190
16
235
21
333
27
370
33
420