Basic characteristics of the Modbus-RTU controller
Addressing
Slave: confi gurable address from 1 to 247
Diffusion
Yes
Transmission speed
9600
Parity
EVEN
Mode
RTU
Electrical interface
RS-485 2W-wired or RS232
Connector type
RJ 45
MODBUS message
Address
Function
Data
CRC verifi cation
8 bits
8 bits
N x 8 bits
16 bits
The format for each byte in RTU mode is:
Code system: 8–bit binary
Bits per Byte: 1 bit of START (start)
8 data bits, the most signifi cant bit is sent the fi rst
1 bit for the parity (Even parity required)
1 bit of STOP (end)
Modbus memory map
Nº
Reg.
Type of register
Description
Range
Data
Default
value
R/W
Comments
General confi guration
9
Coil
Unit status
0
Off
1
R/W
1
Run
7
Coil
Contact CLP
start/stop
0
Contact NO
0
R/W
1
Contact NC
0
Coil
Fans working mode
0
VAV mode
0
R/W
1
COP mode
0
Input Register
Vin
0 - 10
V
R
Analogic input value (V)
1
Input Register
TODA
-30 - 50
ºC
R
Outdoor Air Temperature
(Fresh air)
2
Input Register
TETA
-30 - 50
ºC
R
Extract Air Temperature
(Foul air)
3
Input Register
TEHA
-30 - 50
ºC
R
Exhaust Air Temperature
(Foul air)
4
Input Register
TSUP
-30 - 50
ºC
R
Supply Air Temperature
(Fresh air)