6.3. MOUNTING PROCESS OF AN ADDITIONAL SUPPLY FILTER
The heat recovery unit is supplied with the fi lters already installed. F7 (ePM1 70%) in supply side and M5
(ePM10 50%) in extract side. In addition, it is possible to mount a second fi lter in the unit (accessory).
(For more information see section “Replacement of fi lters”).
6.4. RANGE SPECIFICATIONS
Model
Complete unit
Fan
Weight
(kg)
Air
connections
diameter
(mm)
Nominal
airfl ow
(m
3
/h)
Effi ciency*
(%)
Electrical
supply
Max.
abs.
power
(kW)
Maximum
current
(A)
Speed
(r.p.m.)
Maximum
current
(A)
CADB-HE D 04 BASIC
200
450
87
1/230V, 50Hz
0,2
2,2
3700
0,95
147
CADB-HE D 08 BASIC
250
800
86,4
1/230V, 50Hz
0,4
2,9
2650
1,3
183
CADB-HE D 12 BASIC
315
1.200
85,3
1/230V, 50Hz
0,95
3,5
2550
1,6
190
CADB-HE D 16 BASIC
315
1.600
85,5
1/230V, 50Hz
0,95
4,3
2845
2,0
235
CADB-HE D 21 BASIC
400
2.100
86,7
1/230V, 50Hz
0,9
4,7
1580
2,2
333
CADB-HE D 27 BASIC
400
2.700
83,8
1/230V, 50Hz
1,84
7,5
2450
3,6
367
CADT-HE D 33 BASIC
400
3.300
85,9
3+N/400V, 50Hz
2,2
4,3
2600
2,0
420
CADT-HE D 45 BASIC
600x400
4.500
86,3
3+N/400V, 50Hz
4,43
6,3
2200
3,0
597
CADT-HE D 60 BASIC
700x500
6.100
86,7
3+N/400V, 50Hz
4,43
6,3
2200
3,0
730
CADT-HE D 100 BASIC
1100x610
10.000
88,9
3+N/400V, 50Hz
8,13
11,9
2160
5,8
862
* Wet efficiency referred to nominal airflow, Outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH)
6.5. CONNECTIONS
6.5.1. Connection with air duct
The fans are always blowing out with regard to the machine. Before making the connection of
air lines, consider the existing identifi cation labels in each inlet/outlet of the heat recovery unit.
Outdoor air
Aire exterior
Aria di rinnovo
Air neur
Aussenluft
Extract air
Aire de extracción
Estrazione dal locale
Air repris
Abluft
Exhaust air
Aire de expulsión
Espulsione all esterno
Air rejeté
Fortluft
Supply air
Aire de impulsión
Inmissione
Air Souffl é
Zuluft
6.5.2. Condensate drainage
The units are supplied with 2 drains (one for each circuit). For added security it has to connect two
drains to the condensate discharge pipe. This connection must be made through a pipe of 22 mm
of inner diameter and a fl ange for secure fi xation.
Drainage system
• To ensure the removal of draining condensate from the tray a siphon must be installed with
pressure head difference in mmWG greater than the pressure provided by the fan.
• The horizontal sections should have a minimum slope of 2%.