Figure 4: Restrictions on installation with the space between the tank unit and the
heat pump unit
Heat pump Unit Installation
The surface to which the heat pump unit is installed must be firm, preferably a
concrete pad or block. If the surface is firm there is no need to fix the unit to a base
surface, unless there is a likelihood of high wind or local vibration.
If the heat pump unit and tank unit are to fixed, appropriate fixing devices for the
weight/expected duty should be used. It is permissible to install the Heat Pump on
the side of a wall provide an adequate support is used.
Note: For California installation the Tank section water heater must be braced,
anchored, or strapped to avoid falling or moving during an earthquake. For Tank
size over 52 Gallons (236l) consult your local building jurisdiction for appropriate
bracing designs.
Note: For Florida installation the Heat Pump unit should be installed in accordance
with all local codes regarding Hurricane winds.
Use appropriately treated lumber or pre-fabricated “pump ups” to raise the Heat
Pump unit 4”-6” from the ground – this will allow defrost condensate to drain. In
areas with significant snowfall ensure unit is mounted above the anticipated
snowfall depth.
A Pressure Relief (PR) valve
MUST
be installed during the installation of the tank
unit. This is installed in a defined point near the top of the tank unit. The PR Valve
must have clear drainage where escaping steam or water can flow freely. PR Valve
setting should be 100 Psig.
The installation site must be well drained so that any water accumulating (such as
rain or pipe leakage) will drain away and not enter the heat pump unit and the tank
unit.
Supply water pressure must be a minimum of 29 PSI (200 kPa) to ensure Heat
Pump unit operation – If pressure is below 29 PSI install a booster pump to water
supply.
Caution
Keep the piping run to a minimum
as the longer the pipe run, the
greater the potential for heat loss
.
Side view
Overhead view
Standard layout
(A) Difference in height between
the base of tank and base of
Heat pump should be no more
than: 16ft(
5
m) Max.
>24” or 600mm
(Minimum Separation
Maximum pipe length 50 ft
(
15 m) per
line between Tank & Heat Pump
Unit.
Maximum number of bends
– 6, use
long radius bends not street “L’s”
2”or
more
2”or
more
Содержание GS3-45HPA-US
Страница 11: ...Sanden Heat Pump Installation Manual Page 11 of 36 Figure 7 Main Power Connection...
Страница 29: ...Sanden Heat Pump Installation Manual Page 29 of 36 GS3 45HPA US Dimensions...
Страница 30: ...Sanden Heat Pump Installation Manual Page 30 of 36 Stainless Steel Tank Dimensions...
Страница 31: ...Sanden Heat Pump Installation Manual Page 31 of 36 Wiring Diagram...
Страница 36: ...Sanden Heat Pump Installation Manual Page 36 of 36 Memo SANDEN Heat Pump 40980 44772 Installation Manual US...