S&C Vista SD Скачать руководство пользователя страница 18

18

  S&C Instruction Sheet 695-545

Operation

STEP  4.  

Determine the phase-to-phase relationships of 
the two ways to be phased as follows:

(a)  Remove the test probe of the voltmeter from the 

neutral jack.

(b)  Place one of the test probes on Test Jack 1 of the 

first way and place the other probe on Test Jack 1 
of the second way. Measure the phase-to-phase  
voltage. When comparing the 

same

 phase of the 

two ways, the voltage should be 0.5 Vac or less for 
system voltages through 13.2 kV maximum, and 
between 0.5 Vac and 1.0 Vac for system voltages 
through 29 kV maximum, indicating the cables 
are in phase. See Figure 25 (a).

(c)  Keep the test probe on Test Jack 1 of the first way 

and move the other test probe to Test Jack 2 of 
the second way. Measure the phase-to-phase 
voltage. When comparing 

different

 phases of the 

two ways, the voltage should be 1.7 to 2 times the 
phase-to-neutral voltage measured in Step 3. See 
Figure 25 (b).

(d)  Keep the test probe on Test Jack 1 of the first way 

and move the other test probe to Test Jack 3 of 
the second way. Measure the phase-to-phase 
voltage. Again when comparing different phases 
of the two ways, the voltage should be 1.7 to 2 
times the phase-to-neutral voltage measured in 
Step 3. See Figure 25 (c).

(e)  Repeat Steps 4b through 4d for Test Jack 2 and 

Test Jack 3 of the first way.

(f)  If all the phase-to-phase relationships are 

correct, the cables are in phase and are properly 
installed.

Figure 25. Measure the phase-to-phase relationships of the two 
ways to be phased. When comparing the same phase of the two 
ways, the voltage should be zero or close to zero, indicating the 
cables are in phase. When comparing different phases of the two 
ways, the voltage should be 1.7 to 2 times the phase-to-neutral 
voltage measured in Step 3.

(a)

(b)

(c)

Содержание Vista SD

Страница 1: ...Instructions and Labels 4 Location of Safety Labels 5 Safety Precautions 6 Components 7 Operation Manually Opening or Closing Visi Gap Load Interrupter Switches and Visi Gap Fault Interrupters 9 Closi...

Страница 2: ...ot intended to be a substitute for adequate training and experience in safety proce dures for this type of equipment Read this Instruction Sheet NOTICE Thoroughly and carefully read this instruction s...

Страница 3: ...user s claim All other warranties whether express or implied or arising by operation of law course of dealing usage of trade or otherwise are excluded The only warranties are those stated in Price Sh...

Страница 4: ...ecautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in prod uct or property damage if instructions are not followed Following Safety Instructions I...

Страница 5: ...locked immediately call electric company G 6398 B DANGER Hazardous voltage more than 4000 volts Failure to follow these instructions will likely cause shock burns or death ALWAYS consider all circuits...

Страница 6: ...a door The use of undue force may damage the door latching mechanism 7 Safety Labels Do not remove or obscure any of the DANGER WARNING CAUTION or NOTICE labels 8 ENERGIZED BUSHINGS Always assume the...

Страница 7: ...of load interrupter switches and fault interrupters are optionally available They can be decoupled from the operating mechanisms to permit testing without changing the positions of the switches or fau...

Страница 8: ...nit shown Catalog Number Suffix 924313 E11 Manual handle Fault indicator viewing window optional Potential indication feature optional Overcurrent control Operating mechanism Visible open gap isolatin...

Страница 9: ...t wrench or tool a hex headsocketwrenchortoolwhencatalognumber suffix N is specified into the latching mechanism Rotate the wrench or tool 60 counterclockwise to unlatch the doors See Figure 3 NOTICE...

Страница 10: ...ion of the manual operating handle STEP 5 Retrieve the manual operating handle from its storage location at the top left side of the switchgear assembly See Figure 5 STEP 6 Pull the knob forward at th...

Страница 11: ...way to the stops See Figure 7 a To open the load interrupter switch or fault interrupter rotate the handle counterclockwise b To close the load interrupter switch or fault interrupter rotate the hand...

Страница 12: ...door is closed To close a door equipped with the Penta Latch Mechanism place one hand at the midpoint of the door front near the edge and firmly push the door closed When the latch points are positive...

Страница 13: ...EP 1 Check the POSITION indicators to confirm the fault interrupter has tripped See Figure 14 STEP 2 Retrieve the manual operating handle from its storage location Attach the handle to the shaft of th...

Страница 14: ...TEP 8 Check the POSITION indicators to confirm the fault interrupter is closed See Figure 19 STEP 9 Confirm the position of the isolating disconnect using the large viewing window See Figure 20 STEP 1...

Страница 15: ...of a load interrupter switch or fault interrupter insert a padlock through the operating mechanism and the center hole in the locking collar See Figure 21 Figure 21 The load interrupter switches or fa...

Страница 16: ...etroleum based solvents should not be used on or around Vista SD Underground Distribution Switchgear STEP 2 Unscrew the aluminum cap covering the Potential Indication feature See Figure 22 STEP 3 Atta...

Страница 17: ...be phased as follows a Set the voltmeter for volts ac b Connectoneofthetestprobesofthevoltmeterto the neutral jack of the way to be phased c Place the other test probe on each of the test jacks in tur...

Страница 18: ...ng different phases of the two ways the voltage should be 1 7 to 2 times the phase to neutral voltage measured in Step 3 See Figure 25 b d Keep the test probe on Test Jack 1 of the first way and move...

Страница 19: ...r sources including backfeed test for voltage and properly ground 4 Always assume the bushings are energized unless proved otherwise by test or by visual evidence of an Open Circuit condition at the i...

Страница 20: ...ve green finish 9991363 493 for seafoam green 9991363 488 for equipment green and 9999 061 for red oxide primer See Figure 27 No other finish or primer is approved The area to be touched up should be...

Страница 21: ...withstand tests The presence of these values does not imply a dc withstand rating or performance requirements for the switchgear A dc withstand design test is speci fied for new equipment because the...

Страница 22: ...tance test or a maintenance test The cable system must be taken out of service for this testing An acceptance test is a field test made after installa tion of the power cable system including terminat...

Страница 23: ...cable applying the VLF test source discharging the cable and regrounding the cable WARNING When VLF cable testing has been completed or has been interrupted you must discharge the cable sys tem and t...

Страница 24: ...ed NO C Vacuum interrupter closed NC D Vacuum interrupter open NO E Vacuum interrupter open NC F Isolating disconnect closed NO G Isolating disconnect closed NC H Isolating disconnect open NO J Isolat...

Отзывы: