background image

S&C Instruction Sheet 662-510

7

Safety Precautions

DANGER

Pad-mounted gear contains high voltage. Failure to observe the precautions 

below will result in serious personal injury or death.
Some of these precautions may differ from company operating procedures and 
rules. Where a discrepancy exists, users should follow their company’s operating 
procedures and rules.

1. 

QUALIFIED PERSONS. Access to pad-mounted 

gear must be restricted only to qualified persons. 
See the “Qual ified Persons” section on page 2.

2. 

SAFETY PROCEDURES. Always follow safe 

operat ing procedures and rules.

3. 

PERSONAL PROTECTIVE EQUIPMENT. Always 

use suitable protective equipment, such as rubber 
gloves, rubber mats, hard hats, safety glasses, and 
flash clothing in accordance with safe operating 
procedures and rules.

4. 

SAFETY LABELS. Do not remove or obscure any 

of the “CAUTION,” “WARNING,” or “DANGER” 
labels.

5. 

KEY INTERLOCKS.
•  If optional key interlocks were furnished, they 

must be in place.

•  Check the operating sequence of key interlocks 

to verify proper sequencing.

•  After the pad-mounted gear is installed, either: 

(1) destroy the extra set of keys or (2) make  
them accessi ble only to qualified persons. This 
will maintain the integrity of the key-interlock 
scheme. 

•  Key interlocks are not security locks and are 

not  substitutes for padlocks.

6. 

OPENING DOORS. Do not force doors open. 

Forcing a door open can damage the latching 
mechanism. If optional key interlocks are provided, 
correctly position the interlocks so the doors can be 
opened.

7. 

CLOSING AND LOCKING DOORS.
•  Doors must be securely closed and latched, 

with   padlocks in place at all times unless work is 
being  performed inside the enclosure. 

•  Mini-Rupter Switches have switch-operating-

shaft  access covers located on the sides of the 
pad- mounted gear enclosure. They must be 
closed and  padlocked at all times unless the 
switches are  being  operated. 

8. 

ENERGIZED TERMINALS. Always assume both 

sets of power terminals on any Mini-Rupter Switch 
or fuse are energized unless proved otherwise by 
test, by visual evidence of open-circuit conditions 
on both sets of terminals, or by observing that both 
sets of ter minals are grounded.

9. 

BACKFEED. Mini-Rupter Switches and fuses may 

be energized by backfeed.

10. 

DE-ENERGIZING, TESTING, AND GROUNDING. 

Before touching any device that is to be inspected, 
replaced, serviced, or repaired in the high-voltage 
compartments, always disconnect Mini-Rupter 
Switches and fuses from all power sources 
(including backfeed), test for voltage, and properly 
ground.

11. 

TESTING. Test for voltage on both sets of power 

ter minals of any Mini-Rupter Switch or fuse 
using proper high-voltage test equipment before 
touching any device that is to be inspected, 
replaced, serviced, or repaired in the high-voltage 
compartments.

12. 

GROUNDING.
•  Make sure the pad-mounted gear enclosure is 

properly grounded to the station or facility 
ground.

•  After the gear has been completely disconnected 

from all sources of power and tested for 

 

voltage, install suitable grounding cables in all  
compart ments before touching any device to be 
inspected, replaced, serviced, or repaired in the 
high-voltage compartments.

13. 

SWITCH POSITION.
•  Always confirm the 

Open/Close position of 

Mini-Rupter Switches by visually observing the 
position of the switch blades.

•  Switches may be energized by backfeed.
•  Switches may be energized in any position.

14. 

MAINTAINING PROPER CLEARANCE. Always 

maintain proper clearance from energized 

 

compo nents.

15. 

FUSE STORAGE.
•  Always store fuses in a clean, dry location.
•  Do not store end-fittings, holders, interrupting 

modules, or fuses in termination compartments 
unless the unit is equipped with the optional 
fuse-storage feature (catalog number suffix 
“-E1,” “-E2,” or “-E3”).

Содержание PMH Series

Страница 1: ...and Closing the Doors 10 Switching with Mini Rupter Switches Operating the Mini Rupter Switch 12 Front Barriers 13 Fusing Assembling the Fuse 15 Installing the Fuse in the Mounting 15 Switching with...

Страница 2: ...trieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The application must be within the ratings furnished for t...

Страница 3: ...C SML Mountings Nor do the seller s warranties apply if other than Fault Fiter Electronic Power Fuses S C Switch Blades or selected current limiting fuses are used in conjunction with S C Fault Fiter...

Страница 4: ...tions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you...

Страница 5: ...EITHER RECEIPT NOR POSSESSION THEREOF INFERS OR TRANSFERS ANY RIGHT IN OR LICENSE TO USE THIS DOCUMENT THE SUBJECT MATTER THEREOF OR ANY DESIGN OR TECHNICAL INFORMATION SHOWN THEREON OR ANY RIGHT TO R...

Страница 6: ...arts live until completely de energized tested grounded and tagged or properly identified Do not work on or near this equipment unless you 1 Know and obey your employer s work rules and S C s instruct...

Страница 7: ...s of the pad mounted gear enclosure They must be closed and padlocked at all times unless the switches are being operated 8 ENERGIZED TERMINALS Always assume both sets of power terminals on any Mini R...

Страница 8: ...n and phase identification labels Uni Rupter Interrupter Storage rack holds up to six SM 4 Refill Units or three SMU 20 Fuse Units Ground studs Interphase and end barriers Fault Fiter Electronic Power...

Страница 9: ...ure Circuit diagram Interphase and end barriers for 14 4 kV gear the end barrier is provided with the optional fuse storage feature only S C Mini Rupter Switch Manually operated switches are furnished...

Страница 10: ...s 7 Make sure the enclosure is properly grounded to the station or facility ground Do not return equipment to service unless such grounds are properly made Opening and Closing the Doors Complete the f...

Страница 11: ...en the door is closed To close a door equipped with the Penta Latch Mechanism place one hand at the midpoint of the door front near the edge and firmly push the doorclosed Whenthelatchpointsarepositiv...

Страница 12: ...tch and check the switch position indicator to verify the switch is in the desired position STEP 4 Follow the instructions to open the enclosure doors on page 10 STEP 5 Check the physical position of...

Страница 13: ...rong Station prong WARNING Dual purpose front barriers must be wiped clean before placing them in the Slide in position In addition do not leave dual purpose front barriers in the Slide in position fo...

Страница 14: ...y and carefully withdraw the barrier with the Grappler tool s prong pointed upward as shown in Figure 14 so that as it clears the Slide in position the hooks on the gear settle into the holes in the b...

Страница 15: ...end fittings an SM 4 Refill Unit into each holder or a Fault Fiter Interrupting Module and Control Module into each holder in accordance with the instruction sheet furnished with the fuse unit refill...

Страница 16: ...ional inner barrier panels catalog number suffix G7 are furnished loosen the pentahead bolts and remove the panel Then remove only the dual purpose front barrier associated with the fuse mounting into...

Страница 17: ...ppler tool c Lift the fuse and lower it into its hinge See Figure 19 Make sure the fuse is securely seated in the hinge and then disengage the Grapplertoolfromthefuse SeeFigure20on page 18 DANGER Make...

Страница 18: ...fuse See inset of Figure 22 on page 19 Then with one s face turned away close the fuse with a swift unhesitating stroke See Figure 22 on page 19 If space is tight between the pull ring of the fuse an...

Страница 19: ...ccur only switch three phase loads with the Uni Rupter Interrupter where each phase is carrying 5 or more of the rated connected load current Do not switch unloaded three phase transformers with the U...

Страница 20: ...e to high voltage STEP 2 If optional inner barrier panels catalog number suffix G7 arefurnished loosenthepentahead bolts and remove the panel Then remove only the dual purpose front barrier associated...

Страница 21: ...are in the Open position If the door is closed it will strike the fuse pull ring The door may be closed if the fuse is removed from its mounting STEP 6 S C recommends the dual purpose front barrier as...

Страница 22: ...y should be stored in a clean dry location Do not store end fittings holders interrupting modules or current limitingfusesinhigh voltagecompartments unless the unit is equipped with the optional fuse...

Страница 23: ...se to the upright posi tion If the fuse is blown the target will remain in the extended projecting position Remove the blown fuse from its mounting following the instructions found in the Opening and...

Страница 24: ...RNING Dual purpose front barriers for switch and fuse compartments should be inserted into the open gap of the Mini Rupter Switch or fuse to provide physical isolation for additional security in the e...

Страница 25: ...9999 058 for olive green finish 9999 080 for light gray finish and 9999 061 for red oxide primer No other finish or primer is approved The area to be touched up should be cleaned to remove all oil an...

Страница 26: ...0 seconds The column headed Dc is given as a reference only for those making dc tests and represents values believed to be appropriate and approximately equivalent to the corresponding power frequency...

Страница 27: ...ing currents associated with the applicable loads as well as line charging and cable charging currents typical for distribution systems of these voltage ratings For applications on Ratings for S C Pow...

Страница 28: ...1 All models except PMH 4 With viewing window in door F2 All models except PMH 4 Inner barrier panels a panel inside the enclosure door for each compartment secured by recessed pentahead bolt s G7 All...

Страница 29: ...mil M2 All models In fuse compartments For conductor sizes No 2 through 4 0 M3 PMH 4 5 6 11 19 PMH 7 8 9 PMH 12 Polymer housed metal oxide surge arresters base mounted at switch terminals and bus term...

Страница 30: ...ductor UD cable at all cable connected switch terminals and bus terminals G W PSC for No 6 through 2 0 or G W PAT for No 4 through 250 kc mil copper or aluminum cable U2 All models G W PAT for 3 0 thr...

Страница 31: ...o be purchased from the appropriate current limiting fuse manufacturer The maximum voltage and maximum ampere ratings listed in this table apply when the corresponding current limiting fuse is used Co...

Страница 32: ...line to ground voltage i e fuses with a voltage rating lower than line to line voltage but greater than or equal to maximum system line to ground voltage S C can only recommend such use in the follow...

Отзывы: