S&C Instruction Sheet 662-510 

Appendix A

Table 1. Ratings and Insulation Test Values

Rating, kV

Withstand, kV

Nom.

Max

60-Hz, RMS

Dc

③④

Impulse (BIL)

14.4

25

25

17.0

27

29

36

60

60

50

70

70

  95

125

125

  Maximum voltage ratings are lower than the values listed when cur-

rent-limiting fuses are used. Consult the appropriate current-limiting 
fuse manufacturer for complete fuse ratings.

  Ac withstand tests made on this equipment after shipment by S&C 

should be conducted at no more than 0.75 times the values shown. 
When making ac tests, the time duration for application of the test volt-
age should be limited to less than 10 seconds.

  The column headed “Dc” is given as a reference only for those 

making dc tests and represents values believed to be appropriate and 
approxi mately equivalent to the corresponding power-frequency with-

stand test values specified for components of this voltage class. The 
presence of this column in no way implies any requirement for a dc 
withstand test on these components.

  Dc withstand tests made on this equipment after shipment by S&C 

should be conducted at no more than 0.75 times the values shown. 
When making dc tests, the test voltage should be raised in discrete 
steps—one minute per step.

  With fuses.

  Without fuses.

Dielectric Testing

For the convenience of users who normally perform elec-
trical tests on system components such as pad-mounted 
gear, appropriate withstand test values are given in Table 1. 

Содержание PMH Series

Страница 1: ...and Closing the Doors 10 Switching with Mini Rupter Switches Operating the Mini Rupter Switch 12 Front Barriers 13 Fusing Assembling the Fuse 15 Installing the Fuse in the Mounting 15 Switching with...

Страница 2: ...trieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The application must be within the ratings furnished for t...

Страница 3: ...C SML Mountings Nor do the seller s warranties apply if other than Fault Fiter Electronic Power Fuses S C Switch Blades or selected current limiting fuses are used in conjunction with S C Fault Fiter...

Страница 4: ...tions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you...

Страница 5: ...EITHER RECEIPT NOR POSSESSION THEREOF INFERS OR TRANSFERS ANY RIGHT IN OR LICENSE TO USE THIS DOCUMENT THE SUBJECT MATTER THEREOF OR ANY DESIGN OR TECHNICAL INFORMATION SHOWN THEREON OR ANY RIGHT TO R...

Страница 6: ...arts live until completely de energized tested grounded and tagged or properly identified Do not work on or near this equipment unless you 1 Know and obey your employer s work rules and S C s instruct...

Страница 7: ...s of the pad mounted gear enclosure They must be closed and padlocked at all times unless the switches are being operated 8 ENERGIZED TERMINALS Always assume both sets of power terminals on any Mini R...

Страница 8: ...n and phase identification labels Uni Rupter Interrupter Storage rack holds up to six SM 4 Refill Units or three SMU 20 Fuse Units Ground studs Interphase and end barriers Fault Fiter Electronic Power...

Страница 9: ...ure Circuit diagram Interphase and end barriers for 14 4 kV gear the end barrier is provided with the optional fuse storage feature only S C Mini Rupter Switch Manually operated switches are furnished...

Страница 10: ...s 7 Make sure the enclosure is properly grounded to the station or facility ground Do not return equipment to service unless such grounds are properly made Opening and Closing the Doors Complete the f...

Страница 11: ...en the door is closed To close a door equipped with the Penta Latch Mechanism place one hand at the midpoint of the door front near the edge and firmly push the doorclosed Whenthelatchpointsarepositiv...

Страница 12: ...tch and check the switch position indicator to verify the switch is in the desired position STEP 4 Follow the instructions to open the enclosure doors on page 10 STEP 5 Check the physical position of...

Страница 13: ...rong Station prong WARNING Dual purpose front barriers must be wiped clean before placing them in the Slide in position In addition do not leave dual purpose front barriers in the Slide in position fo...

Страница 14: ...y and carefully withdraw the barrier with the Grappler tool s prong pointed upward as shown in Figure 14 so that as it clears the Slide in position the hooks on the gear settle into the holes in the b...

Страница 15: ...end fittings an SM 4 Refill Unit into each holder or a Fault Fiter Interrupting Module and Control Module into each holder in accordance with the instruction sheet furnished with the fuse unit refill...

Страница 16: ...ional inner barrier panels catalog number suffix G7 are furnished loosen the pentahead bolts and remove the panel Then remove only the dual purpose front barrier associated with the fuse mounting into...

Страница 17: ...ppler tool c Lift the fuse and lower it into its hinge See Figure 19 Make sure the fuse is securely seated in the hinge and then disengage the Grapplertoolfromthefuse SeeFigure20on page 18 DANGER Make...

Страница 18: ...fuse See inset of Figure 22 on page 19 Then with one s face turned away close the fuse with a swift unhesitating stroke See Figure 22 on page 19 If space is tight between the pull ring of the fuse an...

Страница 19: ...ccur only switch three phase loads with the Uni Rupter Interrupter where each phase is carrying 5 or more of the rated connected load current Do not switch unloaded three phase transformers with the U...

Страница 20: ...e to high voltage STEP 2 If optional inner barrier panels catalog number suffix G7 arefurnished loosenthepentahead bolts and remove the panel Then remove only the dual purpose front barrier associated...

Страница 21: ...are in the Open position If the door is closed it will strike the fuse pull ring The door may be closed if the fuse is removed from its mounting STEP 6 S C recommends the dual purpose front barrier as...

Страница 22: ...y should be stored in a clean dry location Do not store end fittings holders interrupting modules or current limitingfusesinhigh voltagecompartments unless the unit is equipped with the optional fuse...

Страница 23: ...se to the upright posi tion If the fuse is blown the target will remain in the extended projecting position Remove the blown fuse from its mounting following the instructions found in the Opening and...

Страница 24: ...RNING Dual purpose front barriers for switch and fuse compartments should be inserted into the open gap of the Mini Rupter Switch or fuse to provide physical isolation for additional security in the e...

Страница 25: ...9999 058 for olive green finish 9999 080 for light gray finish and 9999 061 for red oxide primer No other finish or primer is approved The area to be touched up should be cleaned to remove all oil an...

Страница 26: ...0 seconds The column headed Dc is given as a reference only for those making dc tests and represents values believed to be appropriate and approximately equivalent to the corresponding power frequency...

Страница 27: ...ing currents associated with the applicable loads as well as line charging and cable charging currents typical for distribution systems of these voltage ratings For applications on Ratings for S C Pow...

Страница 28: ...1 All models except PMH 4 With viewing window in door F2 All models except PMH 4 Inner barrier panels a panel inside the enclosure door for each compartment secured by recessed pentahead bolt s G7 All...

Страница 29: ...mil M2 All models In fuse compartments For conductor sizes No 2 through 4 0 M3 PMH 4 5 6 11 19 PMH 7 8 9 PMH 12 Polymer housed metal oxide surge arresters base mounted at switch terminals and bus term...

Страница 30: ...ductor UD cable at all cable connected switch terminals and bus terminals G W PSC for No 6 through 2 0 or G W PAT for No 4 through 250 kc mil copper or aluminum cable U2 All models G W PAT for 3 0 thr...

Страница 31: ...o be purchased from the appropriate current limiting fuse manufacturer The maximum voltage and maximum ampere ratings listed in this table apply when the corresponding current limiting fuse is used Co...

Страница 32: ...line to ground voltage i e fuses with a voltage rating lower than line to line voltage but greater than or equal to maximum system line to ground voltage S C can only recommend such use in the follow...

Отзывы: