   S&C Instruction Sheet 662-510   

13

Switching with Mini-Rupter

®

 Switches

Figure 12. Dual-purpose front barrier for switch in its nor-

mal, suspended position.

Figure 13.  A Grappler Handling Tool being used to lift the 

barrier. Note the door holder is in place and the adjacent 

door is latched closed to reduce exposure to high voltage.

Front Barriers

Before proceeding with the instructions on handling the 
front barriers, refer to the “DANGER” message on page 7.

S&C recommends the dual-purpose front barrier be 

inserted into the 

“Slide-in”

 position when the Mini-Rupter 

Switch is open. When the barrier is in the 

“Slide-in”

position, the switch blades are isolated from the main 
contacts; moreover, the blades are blocked from closing 
if, for any reason, the Mini-Rupter Switch is operated. 

WARNING

Always use a Grappler Handling Tool attached to a 
suitable universal pole to insert, remove, or replace 
front barriers. No other tools are recommended.

Failure to use the proper tools can result in 

damage to the equipment, flashover, and injury.

Grappler Handling Tool

Talon™ 

Handling Tool

Distribution 

prong

Station prong

WARNING

Dual-purpose front barriers must be wiped clean 
before placing them in the 

“Slide-in” position. In 

addi tion, do not leave dual-purpose front barriers 
in the 

“Slide-in” position for more than one week. 

These bar riers are intended for temporary use only 
to isolate the blades of the Mini-Rupter Switch from 
the main con tacts while work is being performed. 
If the barriers are left in the 

“Slide-in” position for 

extended periods of time, there is the possibility 
of corona discharge to the barriers. 

Prolonged 

exposure to corona discharge may damage the 

barriers and result in a flashover and injury.

To insert the barrier in the 

“Slide-in”

 position, use 

an S&C Grappler Handling Tool, catalog number 4423R1, 
attached to and in line with a suitable universal pole

Figures 13 and 14 through 15 on page 14 show the suggested 
insertion method. The Grappler tool’s prong is pointed 
upward when lifting the front barrier.

● 

Use a universal pole 1

¼

 inches (31.8 mm) in diameter and at least 

6 feet (1829 mm) long (S&C catalog number 4452R2-E, or equal) for 
14.4-kV gear; or at least 8 feet (2438 mm) long (S&C catalog number 
4453R2-E, or equal) for 25-kV gear.

 CAUTION

When ready to close the Mini-Rupter Switch, make 
sure that the dual-purpose front barrier is not in the 

“Slide-in” position.

Содержание PMH Series

Страница 1: ...and Closing the Doors 10 Switching with Mini Rupter Switches Operating the Mini Rupter Switch 12 Front Barriers 13 Fusing Assembling the Fuse 15 Installing the Fuse in the Mounting 15 Switching with...

Страница 2: ...trieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The application must be within the ratings furnished for t...

Страница 3: ...C SML Mountings Nor do the seller s warranties apply if other than Fault Fiter Electronic Power Fuses S C Switch Blades or selected current limiting fuses are used in conjunction with S C Fault Fiter...

Страница 4: ...tions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you...

Страница 5: ...EITHER RECEIPT NOR POSSESSION THEREOF INFERS OR TRANSFERS ANY RIGHT IN OR LICENSE TO USE THIS DOCUMENT THE SUBJECT MATTER THEREOF OR ANY DESIGN OR TECHNICAL INFORMATION SHOWN THEREON OR ANY RIGHT TO R...

Страница 6: ...arts live until completely de energized tested grounded and tagged or properly identified Do not work on or near this equipment unless you 1 Know and obey your employer s work rules and S C s instruct...

Страница 7: ...s of the pad mounted gear enclosure They must be closed and padlocked at all times unless the switches are being operated 8 ENERGIZED TERMINALS Always assume both sets of power terminals on any Mini R...

Страница 8: ...n and phase identification labels Uni Rupter Interrupter Storage rack holds up to six SM 4 Refill Units or three SMU 20 Fuse Units Ground studs Interphase and end barriers Fault Fiter Electronic Power...

Страница 9: ...ure Circuit diagram Interphase and end barriers for 14 4 kV gear the end barrier is provided with the optional fuse storage feature only S C Mini Rupter Switch Manually operated switches are furnished...

Страница 10: ...s 7 Make sure the enclosure is properly grounded to the station or facility ground Do not return equipment to service unless such grounds are properly made Opening and Closing the Doors Complete the f...

Страница 11: ...en the door is closed To close a door equipped with the Penta Latch Mechanism place one hand at the midpoint of the door front near the edge and firmly push the doorclosed Whenthelatchpointsarepositiv...

Страница 12: ...tch and check the switch position indicator to verify the switch is in the desired position STEP 4 Follow the instructions to open the enclosure doors on page 10 STEP 5 Check the physical position of...

Страница 13: ...rong Station prong WARNING Dual purpose front barriers must be wiped clean before placing them in the Slide in position In addition do not leave dual purpose front barriers in the Slide in position fo...

Страница 14: ...y and carefully withdraw the barrier with the Grappler tool s prong pointed upward as shown in Figure 14 so that as it clears the Slide in position the hooks on the gear settle into the holes in the b...

Страница 15: ...end fittings an SM 4 Refill Unit into each holder or a Fault Fiter Interrupting Module and Control Module into each holder in accordance with the instruction sheet furnished with the fuse unit refill...

Страница 16: ...ional inner barrier panels catalog number suffix G7 are furnished loosen the pentahead bolts and remove the panel Then remove only the dual purpose front barrier associated with the fuse mounting into...

Страница 17: ...ppler tool c Lift the fuse and lower it into its hinge See Figure 19 Make sure the fuse is securely seated in the hinge and then disengage the Grapplertoolfromthefuse SeeFigure20on page 18 DANGER Make...

Страница 18: ...fuse See inset of Figure 22 on page 19 Then with one s face turned away close the fuse with a swift unhesitating stroke See Figure 22 on page 19 If space is tight between the pull ring of the fuse an...

Страница 19: ...ccur only switch three phase loads with the Uni Rupter Interrupter where each phase is carrying 5 or more of the rated connected load current Do not switch unloaded three phase transformers with the U...

Страница 20: ...e to high voltage STEP 2 If optional inner barrier panels catalog number suffix G7 arefurnished loosenthepentahead bolts and remove the panel Then remove only the dual purpose front barrier associated...

Страница 21: ...are in the Open position If the door is closed it will strike the fuse pull ring The door may be closed if the fuse is removed from its mounting STEP 6 S C recommends the dual purpose front barrier as...

Страница 22: ...y should be stored in a clean dry location Do not store end fittings holders interrupting modules or current limitingfusesinhigh voltagecompartments unless the unit is equipped with the optional fuse...

Страница 23: ...se to the upright posi tion If the fuse is blown the target will remain in the extended projecting position Remove the blown fuse from its mounting following the instructions found in the Opening and...

Страница 24: ...RNING Dual purpose front barriers for switch and fuse compartments should be inserted into the open gap of the Mini Rupter Switch or fuse to provide physical isolation for additional security in the e...

Страница 25: ...9999 058 for olive green finish 9999 080 for light gray finish and 9999 061 for red oxide primer No other finish or primer is approved The area to be touched up should be cleaned to remove all oil an...

Страница 26: ...0 seconds The column headed Dc is given as a reference only for those making dc tests and represents values believed to be appropriate and approximately equivalent to the corresponding power frequency...

Страница 27: ...ing currents associated with the applicable loads as well as line charging and cable charging currents typical for distribution systems of these voltage ratings For applications on Ratings for S C Pow...

Страница 28: ...1 All models except PMH 4 With viewing window in door F2 All models except PMH 4 Inner barrier panels a panel inside the enclosure door for each compartment secured by recessed pentahead bolt s G7 All...

Страница 29: ...mil M2 All models In fuse compartments For conductor sizes No 2 through 4 0 M3 PMH 4 5 6 11 19 PMH 7 8 9 PMH 12 Polymer housed metal oxide surge arresters base mounted at switch terminals and bus term...

Страница 30: ...ductor UD cable at all cable connected switch terminals and bus terminals G W PSC for No 6 through 2 0 or G W PAT for No 4 through 250 kc mil copper or aluminum cable U2 All models G W PAT for 3 0 thr...

Страница 31: ...o be purchased from the appropriate current limiting fuse manufacturer The maximum voltage and maximum ampere ratings listed in this table apply when the corresponding current limiting fuse is used Co...

Страница 32: ...line to ground voltage i e fuses with a voltage rating lower than line to line voltage but greater than or equal to maximum system line to ground voltage S C can only recommend such use in the follow...

Отзывы: