6 S&C Instruction Sheet 1022-540
Hardware and Software
This section explains how the control components monitor the distribution feeder and
manage capacitor bank operation.
The faceplate LCD screen and switches are shown in Figure 1.
Faceplate Features
AUTO/MANUAL switch—
Toggle this switch up to enable
Automatic
control operation
and block commands from the faceplate CLOSE/OPEN switch. Toggle this switch down to
disable
Automatic
operation.
CLOSE/OPEN switch—
Toggle this switch up to send a
Close
command to the capacitor
bank switch. Toggle this switch down to send an
Open
command to the bank switch.
Note:
When the AUTO/MANUAL switch is in the
Auto
position, toggling the CLOSE/OPEN
switch has no effect.
SELECT SETPOINT switch—
Toggle this switch up or down to scroll through setpoint
parameters on the LCD screen.
CHANGE SETPOINT switch—
Toggle this switch up or down to change selected setpoint.
Note:
When the
Faceplate Setpoints Adjustment
setpoint on the
Setup>Miscellaneous
screen is set to the
Protected
state or the AUTO/MANUAL switch is in the
Auto
mode,
toggling the CHANGE SETPOINT switch has no effect. When the
Faceplate Setpoints
Adjustment
setpoint is set to the
Protected
mode, use of a computer with IntelliLink®
software is required to change the settings.
Figure 1. The IntelliCap Control faceplate.
LCD screen
Local comm port
Switches
Test points
10-A load fuse
Faceplate LCD Screen
The control has a 16-character LCD screen that cycles through the list of real-time data,
operating information, logged data, and setpoints. Other operating information, such as a
temperature sensor error or a manual operation delay, are also displayed. When the LCD
screen is cycling automatically, only setpoints for the presently active control strategy are
shown. If the setpoints are scrolled with a faceplate command, the LCD screen shows all
available setpoints. Table 1 on page 7 lists the real-time data, operating information, and
logged data that appears on the LCD screen.
Note:
Because of rounding differences, the IntelliLink software screens and the LCD screen
may display slightly different values for the real-time data and setpoints.