SAMWONTECH
1st Edition of TEMP2020_Series IM : Dec. 15. 2008 Page 52 / 71
5.5 WAIT function
▶
Press [WAIT SET] button on PROTRAM SET menu screen to enter into this screen.
▶
This screen is to set WAIT Function parameter.
▶
WAIT Function established on this screen can be applied to program segment setting on [5.1 Program
PATTERN].
▶
Following screen is explained for CH1, and CH2 uses the same screen as CH1.
※
Description of WAIT Function
Operating condition for WAIT Function
☞
When Process Value does not reach the Wait Operation Setting Zone within Segment Time setting.
Release condition for WAIT Function
☞
When the Process Value reaches to Wait Operation Setting Zone.
WAIT operation will be released and program operation will step to the next segment (N+1).
①
Setup box to set whether or not using WAIT Function.
②
Setup box to establish WAIT ZONE to release WAIT Operation.
③
Set Wait Time to apply when the Process Value does not reach Wait Zone.
☞
When 00.00 default value of WAIT TIME, WAIT operation will be pending infinitely until released.
④
Setup box for applicable range of WAIT Function.
☞
When “All” is selected, Wait is applied to all Segments setting in [5.1 PROGRAM PATTERN].
☞
When “Soak Seg” is selected, Wait is applied only to the soak segment setting in [5.1 PROGRAM
PATTERN].
⑤
Move to CH1 or CH2 screen.
Table 5-5. WAIT USE setting Parameters
Parameter
Range
Units
Default
WAIT USE
UNUSE, USE
ABS
UNUSE
CH1 WAIT ZONE
CH1.EUS(0.00~100.00%)
CH1.EUS
CH1.EUS(0.00%)
CH2 WAIT ZONE
CH2.EUS(0.00~100.00%)
CH2.EUS
CH2.EUS(0.00%)
WAIT TIME
00.00~99.59 (H,M)
ABS
00.00
WAIT USE METHOD
ALL, SEG
ABS
ALL
[Figure 5-10] WAIT SET screen