1st Edition of TEMP2020_Series IM : Dec. 15. 2008 Page 46 / 71
5.2 REPEAT operation
▶
Press [REPEAT SET] button on PROGRAM SET menu screen to enter into this screen.
▶
This screen is to set repeat operation of entire current pattern and partial segment operation after
complete of current operation.
▶
Following screen explains for CH1, and it is same for CH2 screen.
①
Setup box to input pattern number for repeat operation.
②
Setup box to input count number for current entire pattern repeat.
③
Setup box to input next pattern number to run continually after complete of current operation.
④
Setup box to input start segment number for partial repeat operation.
☞
When the starting Segment is ‘1’, it starts with Start Set Point (SSP) regardless of Start Code(STC).
⑤
Setup box to input end segment number for partial repeat operation.
⑥
Set Setup box to input count number for partial repeat operation.
⑦
Displays of experiment name for current pattern.
☞
The experiment name can be set at [5.6 PATTERN NAME].
☞
This Displays is just READ ONLY and cannot be changed on this screen.
⑧
Move to CH1 or CH2 screen.
⑨
Button to set PATTERN END MODE for operation state after complete of operation.
☞
RESET: Make program operation STOP with generating PTEND signal.
☞
SEG HOLD: Stay operation run with holding SP at last segment.
☞
LINK RUN: Resume pattern operation number set as LINK PATTERN.
Table5-2. REPEAT SET PARAMETER
Parameter
Range
Unit
Default
CH1 PATTERN NUMBER
1~40
ABS
1
CH2 PATTERN NUMBER
1~40
ABS
1
REPEAT COUNT
0(infinite)~999
ABS
1
CH1 LINK PATTERN
1~40
ABS
1
CH2 LINK PATTERN
1~40
ABS
1
PATTERN END MODE
RESET, SEG HOLD, LINK RUN
ABS
RESET
START SEG. for Partial repeat
0~99
ABS
0
END SEG. for Partial repeat
0~99
ABS
0
REPEAT COUNT for Partial repeat
0~99
ABS
0
①
②
④
⑧
⑦
⑤
⑥
③
[Figure 5-3] REPEAT SET screen
⑨