PAGE 32 of 79 VULCAIN OIL-FIRED HEATER
LAST UPDATED: JAN 22-2019 COPYRIGHT © SAMUEL JACKSON, INCORPORATED 2018 ALL RIGHTS RESERVED
Prepare to purge the oil line of air by opening the cock at the back of the burner head and
opening the oil valve. The oil mod motor may need to be partially opened in order to
purge air. Air is present in the line if the pressure gauge needle bounces or if air bubbles
are in the flow meter. Oil pressure should be regulated to 20 psi for HO-1 and 60 psi for
HO-4 and HO-7.
Tighten the adjustment screw to raise the pressure or loosen the adjustment screw to
lower the oil pressure. It should be noted that the atomizing air pressure should be set at
50 psi for HO-1 and 120 psi for HO-4 and HO-7.
The
TEST PROGRAM
offers a methodical way to correct problems. Access it by pressing
the wrench button
on the color touch panel’s home screen. The SETUP screen shown below will come up.
Pressing the “TESTS button accesses the
TEST PROGRAM
. This button is only displayed
when the flame is off.
TIPS
The default password is 1234. The user can change this password after accessing the
SETUP screen.
Press the “TESTS”
button to access the
Test Program
Contrast button adjusts the
brightness of the screen
for easier viewing
Press the “HOME” button
to go to main (home)
screen when finished with
TEST PROGRAM