7

2.05  Connection of the opening limit switches and closing limit switches 

OPEN

CLOSE

In the picture the limit switches are shown, 

but in this control unit you can use separately. 

So you can use for example “Opening limit switch” or

 “Closing limit switch”. 

The contacts of the limit switches are normally closed.

If the input of the FCA ( opening limit switches) 

and FCC ( closing limit switches) are not used, 

put the DIP 1 and 2 in ON and exclude FCA and FCC in the DIPA

21 20 19 18 17 16 15 14 13 12 11 10

nd closing limit switch

21 20 19 18 17 16 15 14 13 12 11 10

2.06  Connection of the antenna

If you use  only a small cable for the antenna, 

for the frequency 433.92 Mhz, cut it at 17cm 

and connect it to the terminal board no.21

21 20 19 18 17 16 15 14 13 12 11 10

COM.

COM.

2.07  Check of the connection 

Check  the exactly tension in the terminal boards, all NC red l.e.d. should be turned on.

When the control unit is powered , the lights L.E.D. which are in the inputs, are turned on when there is a closing common contact. 

Normally the red led in the inputs STOP-FOTO-FCC –FCA are always turned on. 

Normally the green led in the control START – PARTIAL OPENING are turned off.

Look LED L1TEST when correct programmed, should flashes constantly or with a single/double flashing.

Check the safeties, the gate should go in the right direction, it should open firstly.  

.

The connection of the opening control START (16-19) or closing (17-19)

can be done with any button or with a normally open contact.

In case of more devices, they should be serial connected.

If you use the terminal board START (16-19) it is possible

to connect a TIMER to program the opening of the gate. 

It is possible to use a timer with automatic re-closing or 

in step-by-step function (see TIMER WITH STEP-BY-STEP FUNCTION) 

The contact of the TIMER should be normally open, and the contact should

be closed when the gate is opening. If the opening connection is available,

the terminal board no.16 should be parallel connected.

TIMER WITH STEP-BY-STEP  FUNCTION ( DIP B 1 OFF -  2 ON)

If you connect a timer in the input START ( no.16-no.19), the gate closes when the timer contact is in OFF position (open 

contact) but only in case the gate is open  and the timer is connected for more than 10 seconds .

2.04  Connection of the control OPENING AND CLOSING  

Содержание START-S2XL

Страница 1: ...ning Limit Switch Closing Limit Switch STOP PHOTO A CLOSING CLOSE START OPEN 12 Vac 200mA BUS DATA COMMON NEGATIVE ANT POSITIVE ANT 230 Vac NEUTRAL EARTH 230 Vac PHASE LIGHT 230Vac LIGHT 230Vac MOTOR...

Страница 2: ...negative impact on the environment and human health To receive more detailed information regarding disposal of your unit we recommend that you contact the competent public agencies the waste collecti...

Страница 3: ...closing if it is working reverse totally and stop 16 OPENING output START control 17 CLOSING input it makes the following cycle CLOSE STOP CLOSE 18 Bus data system 19 Common contact for services and...

Страница 4: ...the ground system connection is more than 30 m a ground plate must be installed in proximity to the control unit If the motors do not have a cable use the 4 x 1 5 mm2 cable open close common ground I...

Страница 5: ...5 Description of the KIT version The kit version includes Box for Control Unit 115mm x 165mm x 65mm Control Card 2 Channel receiver START OPEN and CLOSE 230V AC Control Board...

Страница 6: ...nnections should be serial The photo beams interfere only when closing provoking a total inversion If the input FOTO is not used put the DIP 4 in ON and exclude FOTO in the DIPA 21 20 19 18 17 16 15 1...

Страница 7: ...inputs STOP FOTO FCC FCA are always turned on Normally the green led in the control START PARTIAL OPENING are turned off Look LED L1TEST when correct programmed should flashes constantly or with a si...

Страница 8: ...ill lit for 6 seconds Then 3 In 6 seconds press and release button PULSANTE P1 again LED L1 flashes twice and then regularly as under described LED L1 LED L1 Only for compatible fixed code 1 regular f...

Страница 9: ...to put an additional receiver RX2 or RX4 with a capacity of 200 3000 codes If you are not sure that the memorization has been correctly start from point no 1 but before cancel the previous codes in t...

Страница 10: ...pen It recloses automatically at the end of the pause time This sequence is for the control START connected to the terminal board no 16 and for the programming of the remote controls To deepen go to t...

Страница 11: ...es for the opening time The gate is in PAUSE TIME The relay light stops 7 Press the button PULSANTE P1 to start closing The gate starts closing the relay sounds slowly 8 Program the dip for the person...

Страница 12: ...on May 3 1989 harmonizing the legislation of the member countries regarding electromagnetic compatibility Reference to harmonized standards EN 61000 6 2 EN 61000 6 3 THE PRODUCT COMPLIES with the ess...

Отзывы: