Samsung Electronics
18
1. Checklist :
1) Is input voltage normal?
2) Is AC power linked correctly?
3) Is input voltage of DC regulator IC KA7805 (IC02) normal? (11VDC-12.5VDC)
4) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC)
2. Troubleshooting procedure
Unplug the power cord and
plug it after 5 seconds
Press the Power Button on the
remote control unit to
operate the air conditioner
Check whether two wires
of power cord are
connected correctly to the
terminal block and control board.
Check whether the fuse on the
control board is normal.
FUSE: 3.15[A]/250[V]
Check the output of SMPS
on the control board.
Input power: AC230±15%[V]
IC02 Input: DC 12[V]
IC02 output: DC 5[V]
◆
Check the setting temperature
◆
Check the indoor unit
control board
◆
Check the display board
Reconnect wires correctly
Replace fuse
PCB should be replaced
operate
does not operate
Yes
Yes
Yes
No
No
No
6-2 Fault Diagnosis by Symptom
6-2-1 No Power (completely dead)-Initial diagnosis
DB98_16999A(2)_1 04/3/12 10:27 AM Page 18
Содержание SC07AS2
Страница 4: ...3 Samsung Electronics 1 2 Pressure Graph SC07AS2 SC07AS2A SC09AS2 SC12AS4...
Страница 26: ...MEMO 25 Samsung Electronics...
Страница 31: ...Samsung Electronics 30 7 3 Ass y Control In Indoor Unit SC07AS2 SC07AS2A SC09AS2 DB93 02524B...
Страница 33: ...Samsung Electronics 32 Exploded Views and Parts List SC12AS4 DB93 02539B...
Страница 36: ...35 Samsung Electronics 9 PCB Diagram 9 1 ASS Y MAIN PCB 7K 9K 12K DB93 02447B TOP...
Страница 37: ...Samsung Electronics 36 PCB Diagram BOTTOM...
Страница 44: ...MEMO 43 Samsung Electronics...
Страница 45: ...MEMO Samsung Electronics 44...