Connecting the Unit (Continued)
Centralized Controller
Installing the Centralized Controller
To use a centralized controller, set K6 of SW05 to OFF position.
- To centralized control, the ventilator should be set as MASTER among one
or more ventilators for communication.
MAIN SW01
ADDRESS
RMC SW02
ADDRESS
K5 K6 K7 K8
SW05
Setup Master Ventilator
1
Set K8 of SW05 to OFF position.
2
Set MAIN ADDRESS as 0,1,2 and also set RMC ADDRESS as 0,1,2 as well.
MAIN : Setup switch to designate the address among ventilators
RMC :
Setup switch to designate the address when controlling by
a centralized controller
Master Ventilator
Ventilator
Ventilator
Transmitter
Centralized Controller
MAIN:0
RMC:0
MAIN:1
RMC:1
MAIN:2
RMC:2
Indoor unit RMC ADDRESS
1 2 3 4 5 6 7 8 9 A B C D E F
Number on the centralized controller 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MAIN SW01
ADDRESS
RMC SW02
ADDRESS
K5 K6 K7 K8
SW05