E-
17
ENGLISH
Connecting the Unit
1
Remove the maintenence cover of the ERV wired remote control.
2
Connect the V1, V2 terminal of the ERV wired remote control to the V1, V2
terminal of the ventilator PCB. (DC 12V)
3
Connect the F3, F4 terminal of the transmitter to the F3, F4 terminal of the
each ventilator PCB. (COM2 Communication)
4
Reassemble the maintenence cover and the ERV wired remote control.
The ERV wired remote control is MASTER of COM2 communication, so it can
communicate without separate ADDRESS setting. Up to 16 ventilators can be
connected to a ERV wired remote control at once.
ERV Wired Remote Control and Multiple Ventilators
COM2 (F3, F4)
Ventilator
Ventilator
Ventilator
Ventilator
DC 12V (V1, V2)
ERV Wired Remot Control
RHF_025EE_IM_E_27512_1.indd 17
2007-04-18 ソタネト 5:43:44