SPACE REQUIREMENTS
•
The space suggested below is based on operating condition of outdoor temperature of 35°C.
If operating condition of outdoor temperature is higher than 35°C, try to have more space.
•
Make sure to clear a passage for a person and air flow.
•
Observe the clearances and dimensions as seen below when installing the outdoor unit.
•
If you install several outdoor units at the same place, observe the space for ventilation and free airflow.
•
If the space for ventilation is insufficient, the air conditioner may not generate performance designed.
Keep in mind that SAMSUNG logo is located on the front side of outdoor unit.
When installing 1 outdoor unit
When installing more than 1 outdoor unit
Note
• The installation space mentioned above is minimum suggested clearance.
• To secure enough service space and performance of system, take account of more sufficient
space.
• The required minimum space between outdoor units for service and performance of system
is at least 100mm.
(Unit : mm)
Wall height unrestricted
(Unit : mm)
Wall height restricted
< Case 1 >
300 or mor
e
500 or mor
e
10 or more
200 or more
200 or more
< Case 3 >
The height
of the wall is
unlimited
Front
< Case 2 >
100 or mor
e
500 or mor
e
50 or more
50 or more
Front
300 or mor
e
100 or mor
e
500 or mor
e
< Case 1 >
300 or mor
e
500 or mor
e
10 or more
10 or more
< Case 2 >
50 or more
50 or more
200 or more
300 or more
< Case 3 >
The height of the wall
is unlimited
20 or
more
20 or
more
100 or
more
100 or
more
400 or
more
400 or
more
Front
Front
In case of ‘Case 1’ and ‘Case 2’
• The height of the wall should be 1500mm or less in the front
side.
• The height of the wall should be 500mm or less in the air inlet
side.
• The height of the wall is unlimited in the side.
• If the height of the wall exceeds the above value, the
additional height (h1)/2, (h2)/2 should be added to the
service space(S1), (S2) individually.
1500
h1
500
h2
Fr
ont side
S1+h1/2
S2+h2/2
Air inlet
(Unit : mm)