installing the unit
_29
ENGLISH
Heat Recovery model
Branch with Y-joint
Using MCU
only
Using Y- joint
and MCU
MCU
MCU
Items
Examples
Remarks
Max.
piping
length
Outdoor ~
Outdoor unit
Piping
(Equivalent
piping)
200m below
(220m below)
Using MCU only
a+b+c+d+e+f+g
≤
200m
(220m)
Equivalent pipe
length.
Y joint : 0.5m,
Header : 1m,
MCU : 1m
Using Y-joint and MCU
a+g+m
≤
200m (220m)
Total piping 1000m below
Using MCU only
a+b+c+d+e+f+g
≤
1000m
Using Y-joint and MCU
a+b+c+d+e+f+g+p+h+i+j+k+m
≤
1000m
Piping
10m below
r
≤
10, s
≤
10, t
≤
10m
Equivalent
piping
13m below
r
≤
13, s
≤
13, t
≤
13m
Level
difference
Outdoor ~
Indoor unit
Piping
110m / 40m
*2)
H1
≤
110m/40m
Indoor ~ Indoor
unit
Piping
15m below
H2
≤
15m
Outdoor ~
Outdoor unit
Piping
5m below
H3
≤
5m
MCU~MCU
Piping
15m below
H4
≤
15m
Allowable
length after
branch
The first branch ~
the farthest
Indoor unit
Piping
45m below
Using MCU only
45m
Using Y-joint and MCU
g+m
≤
45m
MCU(Included
EEV)
Piping
20m below
m
≤
20m
Distribution kit
Model
Remarks
Allowable From distribution kit to indoor unit
3m
MEV-A13SA/MEV-A16SA (For 1 indoor unit)
For wall-mounted &
ceiling Indoor unit
*2) As an outdoor unit is located in a lower position than indoor unit, level difference is 40m. If outdoor unit is located in a higher position than indoor
unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision simulating by PDM kit installation Guide software
whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit
The refrigerant amount of the system must be less than 100kg.