Control-KIT Function
• Control-KIT uses EEV to control the amount of refrigerant flow and controls the system through outdoor unit and
wired remote controller.
• Control-KIT outputs the contact signal for AHU fan operation.
Terminal block 1, 2 (Refer to page 10) outputs the AHU fan ON contact signal (220~240V) for AHU when operating
in Cool/Heat/Fan mode. This contact signal output can not be used as power supply for the motor.
• Terminal block 3, 4 (Refer to page 10) is for AHU-KIT control to receive the fan operation status. This input signal
should be simple OPEN/SHORT signal without any extra voltage.
- Normal fan operation : Terminal block 3, 4 is in SHORT.
- Fan is not in operation : Terminal block 3, 4 is in OPEN.
- To use fan feedback to protect your system, set the function switch K12(Refer to page 21) to OFF position.
• Connect 220~240V/50Hz to terminal block 1(L)/2(N).
• You should connect outdoor unit communication cable to communication line (F1, F2)(Refer to page 10).
• V1, V2(Refer to page 10) is power line for the wired remote controller(12V).
F3, F4(Refer to page 10) is communication line for wired remote controller.