AHU-KIT Structure Diagram
Supply Air
Fresh Air
Return Air Exhaust Air
Outdoor Unit
EEV Kit
EEV Control
1 2 3 4 1 2 3 4 1 2 3 4
Eva_in
Sensor
Eva_out Sensor
Gas pipe
Liquid pipe
Communication F1, F2
Simple BMS
(field supply)
External Controller
(field supply)
Room Sensor
Remote Controller
(optional)
ON/OFF SWITCH
OPERATION LAMP
ERROR LAMP
COOLING
HEATING
POWER-OFF
18℃
19℃
20℃
21℃
22℃
23℃
24℃
25℃
26℃
27℃
28℃
Recommended AHU Size
AHU-KIT MODEL
AHU Capacity Allowance (
㎾
)
AHU Internal Heat Exchanger Volume Allowance (
㎤
)
Minimum
Maximum
Minimum
Maximum
MXD-A16K1X025A
7
8.75
1,200
1,500
MXD-A22K1X050A
14
17.5
2,150
2,688
MXD-A22K2X075A
21
26.25
3,100
3,875
MXD-A22K2X100A
28
35
4,000
5,000
※
Evaporating Temperature : 7˚
C
, Superheat : 1˚
C
, Air temperature : 27˚
C
DB/19˚
C
WB
BEFORE INSTALLATION
• When the controllers (External Controller, simple BMS, Remote Controller) are installed simultaneously,
AHU-KIT doesn’t have the priority of control and operates according to the final signal.
(SIMPLE BMS may indicate the different condition of AHU, if AHU was controlled by other controller finally.)