FUNCTION SETTING
(Continued)
• To enable the centralized control (MCM-A202, DMS, S-NET
III
) of the system,
set up the same way as DVM PLUS Series.
• Use SW03 to set up the channel for interface module(MIM-B14). Choose from ‘0’, ‘1’, ‘2’.
• If the SW03 has been set up other than ‘0’, ‘1’ or ‘2’, it will be recognized as ‘2’.
• Use SW04 to set up the RMC address for interface module.
Setting the Controller Address
Example Channel 1, RMC 2
RMC
AHU-KIT Main PBA
�� �� �� ��
��
��
MIM-B14
Interface Module
Channel 2
Channel 0
Channel 1
SW03
Channel
0
Channel 0
1
Channel 1
2
Channel 2
Others
Channel 2
Setting the Main Address
• Main address is the standard address for the communication between the
outdoor unit and the AHU-KIT.
• If the main address is not set up appropriately, communication error can
occur and the AHU-KIT may not operate.
• Use both SW01 and SW02 to set the main address from ‘00’ to ‘99’.
• Ensure that AHU-KIT does not have same address with any other indoor
units connected to the same outdoor unit.
Main address :12
Example
MAIN