6-1. If the trouble is detected by self-diagnosis
6. Self Diagnosis & Trouble Shooting
To do list
Start
Is MAIN PCB
Connector CN30 and CN76 inserted
correctly?
Is R Sensor
unit normal?
YES
Bad contact of connector/
insert correctly
NO
YES
NO
2) If R Sensor has trouble
Is the voltage between
MAIN PCB Connector CN30 -
“6”(White)
and J23 JUMMPER normal?
NO
NO(0.6V > Measurement < 4.6V)
Sensor MICOM/Connector number
R
Connector CN30 -
“6”(White)
to J23 JUMMPER PCB typical
Ground
Voltage measured between 4.6V ~ 0.6V.
Replace the temperature
sensor
Recheck the wire connection
part
Refer to circuit diagram in the manual
DATA1. Temperature table
** Measuring point of resistance value
according to Sensor **
R : CN30 -
“6” ↔ CN76
-"1" measuring
resistance value
** 0Ω: Short trouble /Ω∞: Open trouble
ERROR Code
YES
161