Self-test mode of wired remote controller
Use of self-test mode
0
Please enter your
PASSWORD
Service mode
Service mode
Reset All Service Mode
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
1. If you want to use the various additional functions for your Wired Remote Controller, press the
and
buttons at the
same time for more than 3 seconds.
f
The password entry screen appears.
2. Enter the password, “0202,” and then press the
button.
f
The settings screen for installation/service mode appears.
3. Select Self-Test Mode in Service Mode.
4. Self-Test Mode consists of Self-Test Mode Display that shows operation value satus and menus that can turn each
component on or off.
Self-Test Mode
Self-Test Mode Display
Water Pump
Booster Heater
DHW Valve (3 Way valve)
Zone#1 Valve
Back Up H Water Pump
Back Up H Water Pump
Back Up Boiler
Zone#2 Valve
Mixing Valve
< OFF >
< OFF >
< OFF >
< OFF >
< OFF >
< OFF >
< OFF >
< OFF >
< OFF >
Self-Test Mode Display
Water Inlet Temp.: -00.0
ঐ
to 000.0
ঐ
Water Outlet Temp.: -00.0
ঐ
to 000.0
ঐ
Backup Heater Outlet Temp: -00.0
ঐ
to 000.0
ঐ
Mixing valve Outlet Temp.: -00.0
ঐ
to 000.0
ঐ
Tank Temp: -00.0
ঐ
to 000.0
ঐ
Indoor Ambient Temp.: -00.0
ঐ
to 000.0
ঐ
Indoor Ambient Temp. (Zone2): -00.0
ঐ
to 000.0
ঐ
Flow Temp. Sensor #1(Zone1): -00.0
ঐ
to 000.0
ঐ
Flow Temp. Sensor #2(Zone2): -00.0
ঐ
to 000.0
ঐ
Termostat #1(Zone #1): Coo/Heat
Termostat #2(Zone #2): Coo/Heat
Solar Panel On/Off: On/Off
Self-Test Mode Display
29