No.
Note
No.
Note
⑦
Thermistor
CNS043(White)
1-2: Heater Out
5-6: Eva In
⑧
TB-C(Black)
F3-F4:COMM2 (Wired Remote Controller)
⑨
TB-C(Black)
F1-F2:COMM1 (IN-OUT COMM)
⑩
Water Pump Signal
CNS1(White)
1: Signal
3: Gnd
⑪
Flow Sensor
CNS057(White)
1: DC5V
2: Signal
3: Gnd
4: N.C
⑫
3-Way Valve
CNP501(White)
1: Neutral
3: Signal_NO
5: Signal_NC
⑬
Immersion Heater
TB-A1(Block)
L-N, Output, AC
⑭
Main Power TB-A(Black)
L-N, INPUT, AC
⑮
TB-B(Black)
Terminal No.
Function
Input /output
Max. Current
Description
Remark
B1/B6
Water Pump
AC 230V output
0.5 A
Water INV. pump operation (maximum input power of
pump 100W). (B6 : Lived)
Mandatory
B2/B3/B5
Mixing valve
AC 230V output
22 mA
Mixing Valve operation(B2: CW, B3: CCW)
Option
B4/B5
Backup Boiler
AC 230V output
10 mA
Signal output for Backup Boiler(B5: Neutral)
Option
B7/B8
Water Pump
AC 230V output
0.5 A
Additional Water pump operation (maximum input
power of pump 100W)(B8 : Lived)
Option
B9/B10/
B11/B12
2Way valve #1
AC 230V output
22 mA
2 Way Valve operation for Zone#1 (UFH)
(B9 : NO, B10 : NC, B11: Neutral, B12: Lived)
Option
B13/B14/B11/
B12
2Way valve #2
AC 230V output
22 mA
2 Way Valve operation for Zone#2 (FCU)
(B13 : NO, B14 : NC, B11: Neutral, B12: Lived)
Option
B15/B16/B17/
B18
3Way valve
AC 230V output
22 mA
3 Way Valve operation for DHW
(B17 : NO, B18 : NC, B15: Neutral, B16: Lived)
Option
B19/B20
Thermostats
AC 230V output
22 mA
Power to external thermostat(s)
(B20: Lived)
Option
B21/B22
Thermostat 1
AC 230V input
22mA
Thermostat for zone#1 (UFH) Cooling(B21)/
Heating(B22) Signal
Option
B23/B24
Thermostat 2
AC 230V input
22mA
Thermostat for zone#2 (FCU) Cooling(B23)/Heating(B24)
Signal
Option
B25/B26
Solar Pump
AC 230V input
10 mA
Signal input from Solar Pump / DHW Thermostat
(B26 :Lived)
Option
⑯
Dip Switch(K1~K4)
11
ENGLISH