ENGLISH-41
03
AD
VANCED
OPER
ATION
Water Law for Cooling
•
Outdoor air temperature range : Lower limit
C1
(#2051, Default 30˚C, Range : 25 ~ 35˚C),
Upper limit C2(#2052, Default 40˚C, Range : 35 ~ 45˚C)
- With this default settings, the water outlet temperature by cooling water law can be changed within the outdoor
temperature range of 30 ~ 40˚C.
•
Water out temperature range for floor/FCU applications respectively :
Upper limit
C1
(#2061/2071, Default 25/18˚C), Lower limit C2(#2062/2072, Default 18/5˚C)
- With this default settings, the water outlet temperature by cooling water law can be changed within the range of 5/18
~ 18/25˚C.
•
Type of water law for according to cooling devices(floor/FCU) : #2081(Default “1”(WL1 for floor), “2”(WL2 for FCU or radiator)
External Room Thermostat (Field Option)
•
Terminal #1(#2091, Default “0” for no usage), #2(#2092, Default “0” for no usage)
- To use wired remote controller for heating/cooling operation, both of the above settings should be set to “0”
simultaneously. If not, thermostat controls system.
- Types of water law used by room thermostat operation will follow the FSV settings defined in #2041(heating) and
#2081(cooling) respectively.
- During the thermostat operation, the user has the possibility to shift up or down the target water temperature within
the range of -5 ~ +5˚C.
•
When the remote controller is used, floor valve should be connected to zone #1 and the FCU valve should be separately
connected to zone #2 of the CONTROL KIT PBA.
•
When only floor cooling/heating is installed and if the Water Law or outlet water temperature is too low, 2way valve may
closed and E911 error may occur.
•
When the floor and FCU units are installed together and operating in cooling mode, floor valve may close and E911 may
occur to prevent floor condensation when the outlet water temperature is below 16°C. Therefore FCU should secure
minimum value for the flow rate.
•
Thermostat #2 which controls FCU has the priority for operation modes and the discharge water temperature.
•
Samsung is not responsible for the accidents such as floor condensations which can occur by not connecting the valve to
the zone #1 port of the CONTROL KIT PBA.
EHS_MONO- KIT_IB_05402A-01_BOOK.indb 41
2016-03-29 오후 5:44:22
Содержание MIM-E03*N
Страница 14: ...ENGLISH 14 Description of each control Buttons EHS_MONO KIT_IB_05402A 01_BOOK indb 14 2016 03 29 오후 5 44 03 ...
Страница 85: ...ENGLISH 85 04 OTHERS MEMO EHS_MONO KIT_IB_05402A 01_BOOK indb 85 2016 03 29 오후 5 44 35 ...
Страница 86: ...ENGLISH 86 MEMO EHS_MONO KIT_IB_05402A 01_BOOK indb 86 2016 03 29 오후 5 44 35 ...
Страница 87: ...ENGLISH 87 04 OTHERS MEMO EHS_MONO KIT_IB_05402A 01_BOOK indb 87 2016 03 29 오후 5 44 35 ...