E-
62
Single indoor unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1
Text-2
Text-3
Text-4 Text-5
1
Indoor Temperature
AI
AC_RoomTemp_xx_xxxxxx
°C
2
Set temperature
AV
AC_Temp_Set_xx_xxxxxx
°C
3
Setting lower temperature limit
AV
AC_Cool_LimitTemp_xx_xxxxxx
°C
4
Setting upper temperature limit
AV
AC_Heat_LimitTemp_xx_xxxxxx
°C
5
The power value of an indoor unit after
the basic date
AI
AC_Baseline_kWh_xx_xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI
AC_Baseline_Minute_xx_xxxxxx
Minute
7
Power value within period
AI
AC_Period_kWh_xx_xxxxxx
kWh
8
The number of hours usage of an
indoor unit within period
AI
AC_Period_Minute_xx_xxxxxx
Minute
** 9
Power On/Off
BV
AC_Power_xx_xxxxxx
Off
On
10
Applying lower temperature limit
setting
BV
AC_Cool_Limit_set_xx_xxxxxx
False
True
11
Applying upper temperature limit
setting
BV
AC_Heat_Limit_set_xx_xxxxxx
False
True
** 12
Filter sign status
BI
AC_FilterSign_xx_xxxxxx
False
True
** 13
Filter sign reset
BO
AC_FilterSign_Reset_xx_xxxxxx
False
True
** 14
Operation mode status
MV
AC_Operation_Mode_xx_xxxxxx
Auto
Cool
Heat
Fan
Dry
* 15
Fan speed status
MV
AC_FanSpeed_xx_xxxxxx
Auto
Low
Mid
High Turbo
16
Air flow direction status
MV
AC_FanFlow_xx_xxxxxx
None
Vertical
Horizon
All
** 17
Operation mode limit status
MV
AC_Mode_Limit_xx_xxxxxx
No
Limit
Cool
Only
Heat
Only
** 18
Remote controller limit status
MV
AC_Remocon_Limit_xx_xxxxxx
Enable RC
Disable
RC
Conditional
RC
** 19
Integrated error code of both indoor
unit and outdoor unit
AI
AC_Error_Code_xx_xxxxxx
Refer to list of error code
* 20
SPI setting
BV
AC_SPI_xx_xxxxxx
False
True
* 21
HumanSensor setting
BV
AC_MDS_xx_xxxxxx
False
True
** 22
AC Indoor Notify
NC
AC_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
* 23
Discharge cooling set temperature
AV
AC_DisCoolTemp_Set_xx_xxxxxx
°C/F
* 24
Discharge heating set temperatrue
AV
AC_DisHeatTemp_Set_xx_xxxxxx
°C/F
* 25
Discharge current temperature
AI
AC_DisCurrentTemp_xx_xxxxxx
°C/F
K
Temperature setting range can be different depending on the model and the common
range is as follows:
Auto:
18 ˚C~30 ˚C
Cool:
18 ˚C~30 ˚C
Heat:
16 ˚C~30 ˚C
Fan: Temperature cannot be adjusted
Dry:
18 ˚C~30 ˚C
(*) Mark is optionally supported. For a fresh duct, (**) mark is supported.
BACnet Gateway setting (Continued)
BACnet Point List
Indoor Unit
zvsuhzhktzYU\MihjMs~piptW]W`\hTWXluUGGG]Y