BACnet Gateway setting
y
Connecting outdoor units and BACnet Gateway
- You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway.
K
Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
K
The maximum number of indoor units (including ERV and MCU) that can be connected to
each communication channel of BACnet Gateway RS485 is 128.
- The more outdoor units are connected, the longer time takes for tracking. (Max. 30 minutes)
BMS system
PM 05:45
Touch Centralized Controller
Control &
Monitoring
Schedule
Settings
OnOff
controller
Touch
Centralized
controller
Outdoor
Unit
RS 485
BACnet Gateway
Internet
BMS Engineering
SAMSUNG Engineering
Max 256 Indoor units
(DVM Series)
X
For devices that support new communication, you must set the communication mode of
the channel to 'NEW' from 'System settings
Tracking' menu. Set of Indoor/outdoor units,
with conventional communication type, cannot be connected to BACnet Gateway with new
communication.
X
When setting communication channel mode as 'NEW', the address of virtual centralized
control will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 3: Virtual OnOff controller 14,
Channel 4: Virtual OnOff controller 15