Connecting outdoor unit and DMS2.5.
-
You can control up to 80 outdoor units and 256 indoor units by using DMS2.5.
K
You can connect up to 16 (outdoor) units per each communication channel of the DMS2.5.
K
The maximum number of indoor units (including ERV and MCU) that can be connected to each
communication channel of DMS2.5 RS485 is 128.
-
If the number of connected outdoor unit increases, it may take long time for tracking.
(Max. 30 minutes)
System Architecture
X
For devices that support new communication, you must set the communication mode of
the channel to ‘NEW’ from ‘System settings
£
Tracking’ menu.
Set of Indoor/outdoor units, with conventional communication type, cannot be connected
to DMS2.5 with new communication.
X
When ‘NEW’ is set as communication mode of the channel, virtual OnOff controller address
will be assigned.
( Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 3: Virtual OnOff controller 14,
Channel 4: Virtual OnOff controller 15)
PM 05:45
DMS2.5
SIM/PIM
Outdoor
Unit
Power Meter
OnOff
Controller
Touch
Centralized
controller
Web Client
RMS Center
Internet
S-NET 3
Max 256 Indoor units
(DVM Series)
TCP/IP
R5 485