background image

E-

10

INSTALLING THE INDOOR UNIT

Cutting/Extending the Piping

Make sure that you have the required tools available (pipe cutter, reamer,
flaring tool and pipe holder).

1

To prevent any gas from leaking out, remove all burrs at the cut end of the

pipe, using a reamer.

3

 

            

 Outer Diameter

 (D)       

 Depth

(A) 

 

 

 

 

1/4 inch 

0.05 inch

 

3/8 inch 

0.07 inch

                

1/2 inch  

0.08 inch

Slide a flare nut on to the pipe and modify the flare.

4

 

Outer Diameter 

Torque              

 

 

 

1/4 inch 

10.1~12.3 ft.lb

 

3/8 inch  

18.1~20.3 ft.lb 

                 

1/2 inch  

27.5~30.4 ft.lb 

Align the pipes to be connected and tighten the flare nuts first manually and
then with a torque wrench, applying the following torque.

6

Check that the flaring is correct, referring to the illustrations below for examples of incorrect 

flaring.

5

If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe,
and referring to the illustrations below for examples of edges cut correctly
and incorrectly.

2

Oblique

                  Rough

                   Burr

Inclined

     Damaged Surface

Cracked

Uneven Thickness

D

A

��

O                       

   x                       

   x                                      x

For further details on how to connect up to the outdoor unit and purge the circuit, refer to 

page 23.

7



In case welding the pipe, the gas nitrogen must be blown into the parts.

Содержание MH050FX*A2 series

Страница 1: ...E 1 ENGLISH ...

Страница 2: ...rreinstalltheunit Ifperformedbyunauthorizedpersonnel theseoperationsmay causeelectricshocksorfires Donotplacecontainerswithliquidsorotherobjectsontheunit Allthematerialsusedforthemanufactureandpackagingoftheairconditionerarerecyclable Thepackingmaterialandexhaustbatteriesoftheremotecontrol optional mustbedisposedofinaccordancewithcurrentlaws Theairconditionercontainsarefrigerantthathastobedisposed...

Страница 3: ...GTHE OUTDOOR UNIT Connecting the Cables to the Outdoor Unit 11 Transmitter Installation Optional 14 Checking Correct Earthing 16 Fixing the Unit in Position 16 COMPLETINGTHE INSTALLATION Connecting Up and Purging the Circuit 17 Adding Refrigerant 18 Performing Leak Tests 19 Pipe Installation with Indoor Units 20 Switch Setting and Testing Operation 21 Pipe Checking Operation Auto Addressing Mode 2...

Страница 4: ...sary noise and vibration Position the outdoor unit so that the air flow is directed towards the outside as indicated by the arrows on the top of the unit Maintain sufficient clearance around the outdoor unit as indicated in the diagram on the page opposite Make sure that the water dripping from the drain hose runs away correctly and safely You have just purchased a Free Joint Multi air conditioner...

Страница 5: ...9 2ft 24 6ft Composition A B A B H h Piping length and the height Main power switch 7 86 inch or more 6 29 inch or more 3 93 inch or more 11 8 inch minimum 11 8 inch minimum 23 6 inch minimum CAUTION 9 84ft as minimum pipe length It will reduce noise and vibration This value must be increased at 24 6 ft in case it is connected just one indoor unit System can work with one indoor unit connected but...

Страница 6: ...h Piping length and the height C D 7 86 inch or more 6 29 inch or more 3 93 inch or more Main power switch 23 6 inch minimum 11 8 inch minimum 11 8 inch minimum 23 6 inch minimum CAUTION 9 84 ft as minimum pipe length It will reduce noise and vibration This value must be increased at 24 6 ft in case it is connected just one indoor unit System can work with one indoor unit connected but it is recom...

Страница 7: ...e outdoor unit are blocked by the wall 59 06 or more 78 74 or more The upper part of the outdoor unit and the air outlet is towards the wall 19 69 or more 11 81 or more The upper part of the outdoor unit and the air outlet is opposite the wall 59 06 or more 11 81 or more When front and rear side of the outdoor unit is towards the wall Unit inch Wheninstalling1outdoorunit Space Requirements for Out...

Страница 8: ...11 81 or more 59 06 or more 23 62 or more 23 62 or more 23 62 or more When 3 sides of the outdoor unit are blocked by the wall When front and rear side of the outdoor unit is towards the wall When front and rear side of the outdoor unit is towards the wall When installing more than 1 outdoor unit 11 81 or more 11 81 or more 19 69 or more 19 69 or more The upper part of the outdoor unit and the air...

Страница 9: ...8 Installation Manual The 3 wire power cable and the 2 wire assembly cable are optional If these cables are not supplied use the standard cable approved by IEC standard Please check Connecting the Cables to the Outdoor Unit section InstallingandConnectingtheDrainHoseoftheOutdoorUnit While heating ice may accumulate During the process of defrosting check if condensation draining is adequate For ade...

Страница 10: ... to be connected and tighten the flare nuts first manually and then with a torque wrench applying the following torque 6 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring 5 If you wish to shorten the piping cut it using a pipe cutter taking care to ensure that the cut edge remains at a 90 angle with the side of the pipe and referring to the il...

Страница 11: ... to the model 1 L 2 N 1 L 2 N 1 L 2 N F1 F2 1 L 2 N F1 F2 F1 F2 F1 F2 L N F1 F2 F1 F2 1 2 2 1 1 2 F1 F2 F1 F2 1 2 1 2 B C B C A MH050FX A2 A unit B unit Indoor unit Assembly cable Earth terminal Outdoor unit Main Power supply cable Power cable to indoor units Communication cable to indoor units CableType A CableType B CableType C The specification for cables Earth terminal Earth terminal Earth ter...

Страница 12: ...rminal Earth terminal Earth terminal Power cable to indoor units Earth terminal Main Power supply cable Communication cable to indoor units CableType A CableType B CableType C The specification for cables Connect the power cable to the auxiliary circuit breaker If every pole fails to connect to the power supply it must be incorporated in a wire with a contact opening of 0 12 inch Model Main Power ...

Страница 13: ... 3 54 Power cable to indoor units L inch Cable of indoor unit Remark A 2 36 2 36 3 15 B 2 36 2 36 3 15 C 2 76 2 76 4 33 For 080 only D 3 54 3 54 3 54 For 080 only Communication cable to indoor units L inch Cable of indoor unit Remark A 0 59 0 59 B C For 080 only D For 080 only 1 2 E 1 2 E The designs and shape are subject to change according to the model 1 2 L inch ...

Страница 14: ...e outdoor unit then connect the power and the communication cable between the transmitter and the outdoor unit refer to the figure of page 15 3 If you install a transmitter to an outdoor unit every indoor unit which is connected to an outdoor unit can be controlled simultaneously 4 Each outdoor unit connected to the same centralized controller has its own transmitter Fix the case with bolts Contro...

Страница 15: ... 2 housings on the communication cable Transmittercommunication cable Accessoryinthe transmitter Terminal Block in the outdoor unit TerminalBlockintheoutdoorunit MH080FX A4 MH050FX A2 The designs and shape are subject to change according to the model K1 K2 K3 K4 Change DIPswitch K2 in all indoor units PCB K2 ON OFF INSTALLING THE OUTDOOR UNIT Blue MH050FX A2 MH080FX A4 ...

Страница 16: ...lectrode and its cable 2 The earthing wire for the telephone line cannot be used to earth the air conditioner If the earthing electrode is installed in an area of heavy traffic its wire must be connected securely Checking Correct Earthing The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration particularly if the outdoor unit is to be in...

Страница 17: ...er about 10 minutes This procedure is very important in order to avoid gas leak Turn off the vacuum pump Remove the hose of the low pressure side of manifold gauge 5 Set valve cork of both liquid side and gas side of packed valve to the open position 6 Mount the valve stem nuts and the service port cap to the valve and tighten them at the torque of 13 2 ft lb with a torque wrench 7 Check for gas l...

Страница 18: ...auge show 0 1MPa 76cmHg after about 30 minutes This procedure is very important in order to avoid gas leak Turn off the vacuum pump Remove the hose of the low pressure side of manifold gauge 5 Set valve cork of both liquid side and gas side of packed valve to the open position 6 Mount the valve stem nuts and the service port cap to the valve and tighten them at the torque of 13 2 ft lb with a torq...

Страница 19: ... WITH R 410A after opening valves Before opening valves discharge all the nitrogen into the system and create vacuum according to page 23 24 After opening valves check leaks using a leak detector for refrigerant PUMP DOWN before disconnecing t the refrigerant connections for unit repair removal or disposal Pump down is an operation intended to collect all the system refrigerant in the outdoor unit...

Страница 20: ...as A B C D MH052F CA Install pipes between indoor and outdoor units orderly as D Examples 2Rooms MH035FNCA MH052FNCA A B C D MH035FNCA MH052FNCA o A B C D MH035FNCA MH052FNCA x A B C D MH035FNCA MH052FNCA x 3Rooms MH026FNCA MH026FNCA MH052FNCA A B C D MH026FNCA MH026FNCA MH052FNCA o A B C D MH026FNCA MH026FNCA MH052FNCA x Aunit Bunit Cunit Dunit COMPLETING THE INSTALLATION OUTDOOR UNIT ...

Страница 21: ...oor unit A 01 communication with indoor unit B 02 communication with indoor unit C 03 communication with indoor unit D To complete the installation perform the following checks and tests to ensure that the air conditioner is operating correctly COMPLETING THE INSTALLATION In case of Manual address mode you can do pipe check operation for check whether you connect the pipes correctly or not But you...

Страница 22: ...SwitchSettingandTestingOperation Cont COMPLETING THE INSTALLATION TYPE PICTURE MODEL TO SET ADDRESSING MANUALLY BY ROTARY SWITCH SW02 RAC MH026FNCA MH035FNCA MH052FNCA SLIM DUCT MH026FECA MH035FECA MH052FECA ...

Страница 23: ...ode try run or heat mode try run Cool mode try run Push the K2 button three times Heat mode try run Push the K2 button once After 12 minutes of stationary condition check each indoor unit air treatment Cooling mode indoor unit check Inlet air temp Outlet air temp From 10 K to 12 K indicative delta T Heating mode indoor unit check Outlet air temp Inlet air temp From 11 K to 14 K indicative delta T ...

Страница 24: ...on the PCB of outdoor unit Contact the authorized service technician or dealer for setting and changing the Ampere Limit Switch Before changing the Ampere Limit Switch turn off the main power of the system K 1 K 2 K 3 DIS01 SW02 SW01 K 4 DIS02 The designs and shape are subject to change according to the model Outdoor PCB Display Ampere Switch Selection MH050FX A2 MH080FX A4 Switch 3 4 13 5A Defaul...

Страница 25: ...or ServiceTechnician Outdoor PCB Display Switch Indoorunit address View data display K4View mode Display changes Push Display Explanation Push Display Explanation 0 Present Compressor Frequency 8 Discharge temperature 1 Target Compressor Frequency 9 OLP temperature 2 Order Compressor Frequency 10 Condenser temperature 3 EEV0 current step 11 Outdoor temperature 4 EEV1 current step 12 First current ...

Страница 26: ...pleteing pipe check operation it shows on the display PCB The left display DIS01 will show sequentially the following message 00 Estabilished communication with indoor unit A 01 Estabilished communication with indoor unit B 02 Estabilished communication with indoor unit C 03 Estabilished communication with indoor unit D 00 Estabilished communication with indoor unit A Function of Step 3 Mode Funct...

Страница 27: ...of pipe check operation Check piping connection and setting No pipe check operation check occasion try to operation after the installation through auto addressing mode without pipe check operation Check setting The number of Indoor unit mismatched Check electrical connection and setting Communication error between the outdoor and indoor unit Check electrical connection and setting Outdoor communic...

Страница 28: ...ge and service port Outdoor unit overload Safety control Compressor stop check pipe lenght refrigerant leakage charge Outdoor unit high discharge temperature Safety control Compressor stop check pipe lenght refrigerant leakage charge Outdoor unit EEV open Stopped indoor unit s Self diagnosis Outdoor unit EEV open operating indoor unit s Self diagnosis High temperature over 86 F of outdoor as heati...

Страница 29: ......

Страница 30: ......

Страница 31: ...ENGLISH FreeJointMultiAirConditioner Cooling and Heating INSTALLATION MANUAL Free Joint MH050FX A2 MH080FX A4 DB98 29164A 1 S E F ENGLISH ESPAÑOL FRANÇAIS ...

Отзывы: