22 English
PREP
ARA
TION
Check before use
Efficiency control
y
DVM CHILLER’s water outlet temperature is controlled according to the water outlet
temperature average value of all units which operates by pumps in a module. However,
if you set “Use” for an external water temperature sensor, it controls the water outlet
tmeperature according to a temperature value from the sensor.
y
Only one unit with the highest priority operates, and if the unit operates with the
optimum efficiency, a unit with the following priority will operate.
y
When all units reach efficient operating condition, each unit operates at capacity
between efficient operating condition and the maximum capacity condition.
y
When all units reach efficient operating condition and the water outlet tmeperature
reaches close to the set temperature, the unit with the lowest priority controls descent of
compressor operating capacity.