BASIC INSTALLATION TIPS

SIZING

Basic sizing is 200-250 sq. ft. per 12,000 BTU/h.

Computer/Data Rooms:

Basic sizing is 400-450 sq. ft. per 12,000 BTU/h.

Commercial/Retail:

Basic sizing is 550-600 sq. ft. per 12,000 BTU/h.

Residential:

LOW AMBIENT COOLING

As standard, these units have a low ambient cooling capability down to 10ºF 
outdoor temperature.

Computer/Data Rooms and Commercial:

THESE UNITS CANNOT OPERATE IN COOLING BELOW 10ºF AMBIENT 

TEMPERATURE UNLESS EQUIPPED WITH AN APPROVED WIND BAFFLE TO 

PROTECT THE OUTDOOR UNIT. SHOULD A WIND BAFFLE BE INSTALLED, UNIT 

PERFORMANCE CAN BE EXPECTED DOWN TO 0ºF OUTDOOR TEMPERATURE. 

PLEASE NOTE THAT IF A PROLONGED OFF CYCLE IS EXPERIENCED IN 

OUTDOOR TEMPERATURES BELOW 10ºF, THE UNIT MAY NOT RESTART UNTIL 

THE TEMPERATURE RISES ABOVE 14ºF.

R410A REFRIGERANT

Higher pressures (close to double) than R22, but the operating temperatures 
are very similar to those with R22.

For example:

A saturated suction temperature of 45ºF = Suction Pressure of 130 psig

R410A:

A saturated suction temperature of 45ºF = Suction Pressure of 76 psig

R22:

•   Minimize the time that the system is open to the atmosphere.
•   Ensure that a deep vacuum is pulled on the system - 200 microns or less.
•   Do not install any sight glasses or filter driers in the line set.

NOTE: It is not necessary to remove refrigerant for line sets shorter than 

the specified length of the factory charge.

Содержание max mini-split units

Страница 1: ...WWW SUNLIGHTSUPPLY COM Distributed by BASIC TECHNICAL INFORMATION FOR SAMSUNG MAX MINI SPLIT UNITS...

Страница 2: ...0 16 oz ft over 25 ft CHARGE FOR LINE RUN LENGTHS Length 25 35 45 50 Added Charge oz 0 1 6 3 3 4 0 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconnecting Wir...

Страница 3: ...OR LINE RUN LENGTHS Length 25 35 45 55 65 75 85 95 98 Added Charge oz 0 1 6 3 2 4 8 6 4 8 0 9 6 11 2 11 68 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconnec...

Страница 4: ...LINE RUN LENGTHS Length 25 35 45 55 65 75 85 95 98 Added Charge oz 0 4 3 8 6 12 9 17 2 21 5 25 8 30 1 32 25 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconne...

Страница 5: ...quired to control MAX models with Samsung central control options upper level control Includes sub PCB 4 crimp wire connectors wire harness and sub PCB cover sub PCB Wire Harness sub PCB 1 With the po...

Страница 6: ...ntly pull this wire upward and out of the unit 3 Connect the PCB to the PCB wire harness a and to the sub PCB wire harness b NOTE the sub PCB wire harness is included with the wired controller a b 4 R...

Страница 7: ...red controller wires already installed pull the wires through the front of the indoor unit Cut the 2 small plastic connectors off the ends of the sub PCB wire harness the ends of the red blue and yell...

Страница 8: ...CAN BE EXPECTED DOWN TO 0 F OUTDOOR TEMPERATURE PLEASE NOTE THAT IF A PROLONGED OFF CYCLE IS EXPERIENCED IN OUTDOOR TEMPERATURES BELOW 10 F THE UNIT MAY NOT RESTART UNTIL THE TEMPERATURE RISES ABOVE...

Страница 9: ...an adverse affect on the system s ability to properly return oil to the compressor Over time this will cause inconsistent performance error codes and premature failure of components Ceiling Cassette...

Страница 10: ...Distributed by...

Отзывы: