installing your air conditioner
_21
ENGLISH
Indoor Unit Setting
1.
Before installing the indoor unit, assign an address to the
indoor unit according to the air conditioning system plan.
2.
The address of the indoor unit is assigned by adjusting
MAIN(SW01, SW02) and RMC(SW03, SW04) rotary switches.
K9K10K11K12
K5K6K7K8
No.
Function
ON
OFF
SW06
K5
Heating Current Temperature
Compensation
+2°C
+5°C
K6
Filter Time
1000
hours
2000
hours
K7
Hot Water Heater
Not use
Use
K8
-
-
-
Setting MAIN Address
The MAIN address is for communication between the
indoor unit and the outdoor unit. Therefore, you must
set it to operate the air conditioner properly.
You can set the MAIN address from ‘00’ to ‘99’ by mixing
SW01 and SW02.
The MAIN address from ‘00’ to ‘99’ should differ from
each other.
Check the indoor unit address on the plan that you are
to install and set the address according to the plan.
You may not need to set MAIN address if you selected
Auto Address Setting from the outdoor unit: see details
on the outdoor unit installation manual.
Note
When MAIN address is set as “12”.
For Example
Setting RMC Address
The SW03 and SW04 RMC switch is the address setting
switch for controlling the indoor unit with the centralized
controller.
You must set the SW03, SW04 and K2 switch when using
the centralized controller.
You don’t have to set the SW03 and SW04 RMC switch
when not using the centralized controller.
When RMC address is set as “12”.
For Example
SW01
SW02
SW03
SW05
SW06
SW07
SW04
No.
Function
ON
OFF
SW07
K9
Indoor Expansion Valve
For Heating Stop
Fix 80 step
0 or 80 step
K10
Wired Remocon Group
Master
Not use
Use
K11
External control
Not Use
Use
K12
-
-
-
Additional Functions
K1K2K3K4
No.
Function
ON
OFF
SW05
K1
-
-
-
K2
Centralized controller
Not use
Use
K3
-
-
-
K4
Drain pump
Not use
Use
The designs and shape
are subject to change
according to the model.
SW03
SW04
Duct type_IB_E_29810-1.indd 21