installing your air conditioner

Indoor Unit Installation

It is recommended to install the Y-joint before installing the 
indoor unit.

1.

Place the pattern sheet on the ceiling at the spot where you 
want to install the indoor unit.

  

  Since the diagram is made of paper, it may shrink 
or stretch slightly due to temperature or humidity. 
For this reason, before drilling the holes maintain 
the correct dimensions between the markings.

Note

2.

Insert bolt anchors, use existing ceiling supports or  
construct a suitable support as shown in figure.

3.

Install the suspension bolts depending on the ceiling type.

         CAUTION

   

  

 

Ensure that the ceiling is strong enough to 
support the weight of the indoor unit.  
Before hanging the unit, test the strength  
of each attached suspension bolt.

   

 

   If the length of suspension bolt is more than 

1.5m, it is required to prevent vibration.

   

   If this is not possible, create an opening on 

the false ceiling in order to be able to use it 
to perform the required operations on the 
indoor unit.

4.

Screw eight nuts to the suspension bolts making space for 
hanging the indoor unit.

           

 

CAUTION

      

 

You must install the suspension bolts more 
than four when installing the indoor unit.

   

Concrete

Suspension bolt(3/8" or M10)

Hole in anchor

Hole in plug

Insert

Ceiling support

5.

Hang the indoor unit to the suspension bolts between two nuts.

Piping must be laid and connected inside the  
ceiling when  suspending the unit. If the ceiling is 
already constructed, lay the piping into  
position for connection to the unit before  
placing the unit inside the ceiling.

Note

6.

Screw the nuts to suspend the unit.

7.

Adjust level of the unit by using measurement plate for all 4 sides.

For proper drainage of condensate, give a 
10mm(3mm) slant to the left or right side of the 
unit which will be connected with the drain hose, 
as shown in the figure. Make a tilt when you wish to 
install the drain pump, too.

Note

AVXDS



Performing Leak Test & Insulation

LEAK TEST WITH NITROGEN(before opening valves)

In order to detect basic refrigerant leaks, before recreating the 

vacuum and recirculating the R410A, it’s responsible of installer 

to pressurize the whole system with nitrogen(using a pressure 

regulator) at a pressure above 4.1MPa(gauge).

LEAK TEST WITH R410A(after opening valves)

Before opening valves, discharge all the nitrogen into the  

system and create vacuum. After opening valves check leaks 

using a leak detector for refrigerant R410A.

Leak test

Discharge all the nitrogen to create a vacuum and 

charge the system.

CAUTION

AVXDU



Rubber

1.

To avoid condensation problems, place 

T13.0 or thicker 

Acrylonitrile Butadien Rubber 

separately around each  

refrigerant pipe.

  

  Always make the seam of pipes face upwards.

Note

   

Once you have checked that there are no leaks in the system,  

you can insulate the piping and hose.

Insulation

No gap

NBR(T13.0 or thicker)

Installation Part

  AVXDU



: 10mm 

AVXDS



: 3mm

Drain hose port

10mm(3mm)

Leak check

Leak check

Duct type_IB_E_29810-1.indd   18

2008-11-12   16:28:10

Содержание AVXDS Series

Страница 1: ... Cost Efficient System Your new air conditioner not only provides maximum cooling power in the summer but can also be an efficient heating method in the winter with the advanced Heat pump system This technology is up to 300 more efficient than electrical heating so you can further reduce its running cost Now meet year round needs with one air conditioner Flexible installation Duct type air conditi...

Страница 2: ... NOT touch Follow directions carefully Unplug the power plug from the wall socket Make sure the machine is grounded to prevent electric shock Call the contact center for help Recommended instructions or useful information for use These warning signs are here to prevent injury to you and others Please follow them carefully After reading this section keep it in a safe place for future reference SEVE...

Страница 3: ...Consult the place of purchase or a contact center to disassemble or reinstall the air conditioner Potential risk of unit malfunction water leakage electric shock or fire Consult the place of purchase or contact center to install the air conditioner Improper installation carries a risk of unit malfunction water leakage electric shock or fire If installing in specialty areas such as a factory comple...

Страница 4: ...from power supply before it is repaired or disassembled CAUTION SIGNS Connect the refrigerant tubes first then the electrical lines when installing the unit Always disassemble the electric lines before the refrigerant tubes Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual The manufacturer shal...

Страница 5: ...cur due to the ballast of the lighting apparatus For maximum safety installers should always carefully read the following warnings Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place w...

Страница 6: ... control is not used for a long period of time remove the batteries to prevent leakage of electrolyte When cleaning the outdoor unit touch the heat exchanger radiator fins with extreme care Wearing thick gloves can protect your hands Make sure that the condensed water dripping from the drain hose runs out properly and safely Store the operation and installation manual in a safe location and rememb...

Страница 7: ...ord of the indoor and outdoor units in the protection tube Connect the power cable to the auxiliary circuit breaker You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication cable Maximum length of power cable is decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker MCCB ELB should ...

Страница 8: ...eadset USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they purc...

Страница 9: ...efficiency Please read the user manual to get started and to make the best use of the air conditioner SLIM DUCT TYPE MA DUCT TYPE Your air conditioner may look slightly different from the illustration shown above depending on your model Air intake Air outlet Ceiling Air filter the return air side Air intake Air outlet Ceiling Air filter the return air side Duct type_IB_E_29810 1 indd 10 2008 11 12...

Страница 10: ...nditioner stops heating The air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air conditioner operates again normally The unit will not operate when it starts to de ice Fan Fan may not operate for about 3 5 minutes at the beginning to prevent any cold blasts w...

Страница 11: ...rear side panel to the right side 2 Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy then rinse it with running water and dry it in a ventilated area For best conditions repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter back in its original position...

Страница 12: ...ns repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter back in its original position The illustration shown above may differ from your depending on your model After cleaning the filter press the Filter Reset button on the remote control for 2 seconds to reset the filler schedule ...

Страница 13: ... filter 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat exchanger on the inside of the unit 2 Clean the electric components with jets of air 2 Verify that all the electric components are firmly tightened 2 Clean the fan ...

Страница 14: ...ting Anti protection of internal battery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the compressor of the outdoor unit after it has been started If the heat pump is operating in Heat mode De ice cycle is actuated to remove frost from an outdoor unit that...

Страница 15: ...fan speed does not change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the remote control after you have set the time Odors permeate in the room during operation Check if the appliance is running in a smoky area or if there is a smell entering from outside O...

Страница 16: ...off or drops on the floor HEATING 27 C or less 20 C to 24 C Internal protection triggers and the air conditioner will stop DRYING 18 C to 32 C 5 C to 43 C Condensation may occur on the indoor unit with risk to have either water blow off or drops on the floor The standardized temperature for heating is 7 C If the outdoor temperature drops to 0 C or below the heating capacity can be reduced dependin...

Страница 17: ...ust be laid and connected inside the ceiling when suspending the unit If the ceiling is already constructed lay the piping into position for connection to the unit before placing the unit inside the ceiling Note 6 Screw the nuts to suspend the unit 7 Adjust level of the unit by using measurement plate for all 4 sides For proper drainage of condensate give a 10mm 3mm slant to the left or right side...

Страница 18: ...art or hanger of pipe Add the additional insulation if the insulation plate gets thinner CAUTION Additional insulation Refrigerant pipe insulation a 3 a Hanger Drain pipe and Drain Hose Installation 1 Install the drain hose as short as possible Give a 3mm slant to the drain hose for proper drainage of condensate Secure the drain hose with the cable tie not to be separated from the unit The drain p...

Страница 19: ...of each indoor unit Refer to each installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units Coef 1 55 Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Without the drain pump 1 1 5m Horizontal dra...

Страница 20: ...dress according to the plan You may not need to set MAIN address if you selected Auto Address Setting from the outdoor unit see details on the outdoor unit installation manual Note When MAIN address is set as 12 For Example Setting RMC Address The SW03 and SW04 RMC switch is the address setting switch for controlling the indoor unit with the centralized controller You must set the SW03 SW04 and K2...

Страница 21: ...0900 SAMSUNG 0900 7267864 0 10 Min www samsung com nl NORWAY 3 SAMSUNG 7267864 www samsung com no POLAND 0 801 1SAMSUNG 172678 022 607 93 33 www samsung com pl PORTUGAL 80820 SAMSUNG 726 7864 www samsung com pt SLOVAKIA 0800 SAMSUNG 726 7864 www samsung com sk SPAIN 902 1 SAMSUNG 902 172 678 www samsung com es SWEDEN 075 SAMSUNG 726 78 64 www samsung com se U K 0845 SAMSUNG 7267864 www samsung com...

Страница 22: ...ities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com global register Duct Type Series Slim duct AVXDS MA duct AVXDU Duct type_IB_E_29810 1 indd 23 2009 05 08 ソタタ 10 26 20 ...

Отзывы: