installing your air conditioner

 

_19

ENGLISH

2.

Wind insulating tape around the pipes and drain hose 
avoiding to compress the insulation too much.

3.

Finish wrapping insulating tape around the rest of the  
pipes leading to the outdoor unit.

4.

The pipes and electrical cables connecting the indoor unit 
with the outdoor unit must be fixed to the wall with  
suitable ducts.

   



CAUTION

Must fit tightly against  

body without any gap.

Insulation cover pipe

Indoor unit

Be sure to overlap 

the insulation

Insulation pipe

All refrigerant connection must be accessible, in order 

to permit either unit maintenance or removing it  

completely.

CAUTION

5.

Select the insulation of the refrigerant pipe. 

   

Insulate the gas side and liquid side pipe referring to the 
thickness according to the pipe size.

 

 The thickness according to the pipe size is a standard of 
the indoor temperature of 27°C and humidity of 80%.  
If installing in an unfavorable conditions, use thicker one.

   

Insulator’s heat-resistance temperature should be more 
than 120°C.

Pipe size 

(mm)

Minimum thickness  

of insulation (mm)

Remarks

PE foam EPDM 

foam

Ø6.35~Ø15.88

13

10

If you install the pipe  

underground, at the seaside,  

a spa or on the lake, use 1 grade 

thicker one according to the 

pipe size.

-

25

19

 

   

Install the insulation not to get wider and use the 

adhesives on the connection part of it to prevent 

moisture from entering.

 

   

Wind the refrigerant pipe with insulation tape  

if it is exposed to outside sunlight.

 

   

Install the refrigerant pipe respecting that the  

insulation does not get thinner on the bent part or 

hanger of pipe. 

 

   

Add the additional insulation if the insulation 

plate gets thinner.

CAUTION

Additional insulation

Refrigerant pipe insulation

a×3

a

Hanger

Drain pipe and Drain Hose Installation

1.

Install the drain hose as short as possible.



 Give a 3mm slant to the drain hose for proper 
drainage of condensate.



 Secure the drain hose with the cable-tie not to 
be separated from the unit.

   

The drain pump connection port is used when 
using a drain pump.

Note

2.

Insulate the drain hose and then fix it as a picture.



 Assemble flexible hose with clamps between 
indoor unit and drain pipe.



 Flexible hose clamps should be assembled 
tightly to prevent being loosen. If it is loosen,  
it may cause water drops.

Note

AVXDS



AVXDU



1.

Unscrew the 4 tapped screws to remove the cover of the 
drain hose connection port.

2.

Insert the flexible hose to the drain hose port. 

Fix the flexible hose to the indoor unit with the 
supplied cable clamp securely. (Use the screwdriver to 
fix the flexible hose securely.)

Note

3.

Install the drain hose so that its length can be as short as 
possible. Internal diameter of the drain hose should be the 
same or slightly bigger than the external diameter of the 
drain hose port.

  

 Inner diameter of the drain hose



Give a slightly slant to the drain hose for 
proper drainage of condensate.



 Fix the flexible hose to the PVC with the 
supplied cable tie securely.

Note

4.

Wrap the drain hose with the insulation drain as shown in 
figure and secure it.

Flexible hose

Insulation

Cable-tie

Clamp

Cable clamp

Indoor 
unit

Cable-tie

Insulation drain hose

Insulation cover drain



CAUTION

Must fit tightly against  
body without any gap.

No gap

Drain hose connection port

32mm 

(Inner diameter)

Duct type_IB_E_29810-1.indd   19

2008-11-12   16:28:11

Содержание AVXDS Series

Страница 1: ... Cost Efficient System Your new air conditioner not only provides maximum cooling power in the summer but can also be an efficient heating method in the winter with the advanced Heat pump system This technology is up to 300 more efficient than electrical heating so you can further reduce its running cost Now meet year round needs with one air conditioner Flexible installation Duct type air conditi...

Страница 2: ... NOT touch Follow directions carefully Unplug the power plug from the wall socket Make sure the machine is grounded to prevent electric shock Call the contact center for help Recommended instructions or useful information for use These warning signs are here to prevent injury to you and others Please follow them carefully After reading this section keep it in a safe place for future reference SEVE...

Страница 3: ...Consult the place of purchase or a contact center to disassemble or reinstall the air conditioner Potential risk of unit malfunction water leakage electric shock or fire Consult the place of purchase or contact center to install the air conditioner Improper installation carries a risk of unit malfunction water leakage electric shock or fire If installing in specialty areas such as a factory comple...

Страница 4: ...from power supply before it is repaired or disassembled CAUTION SIGNS Connect the refrigerant tubes first then the electrical lines when installing the unit Always disassemble the electric lines before the refrigerant tubes Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual The manufacturer shal...

Страница 5: ...cur due to the ballast of the lighting apparatus For maximum safety installers should always carefully read the following warnings Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place w...

Страница 6: ... control is not used for a long period of time remove the batteries to prevent leakage of electrolyte When cleaning the outdoor unit touch the heat exchanger radiator fins with extreme care Wearing thick gloves can protect your hands Make sure that the condensed water dripping from the drain hose runs out properly and safely Store the operation and installation manual in a safe location and rememb...

Страница 7: ...ord of the indoor and outdoor units in the protection tube Connect the power cable to the auxiliary circuit breaker You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication cable Maximum length of power cable is decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker MCCB ELB should ...

Страница 8: ...eadset USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they purc...

Страница 9: ...efficiency Please read the user manual to get started and to make the best use of the air conditioner SLIM DUCT TYPE MA DUCT TYPE Your air conditioner may look slightly different from the illustration shown above depending on your model Air intake Air outlet Ceiling Air filter the return air side Air intake Air outlet Ceiling Air filter the return air side Duct type_IB_E_29810 1 indd 10 2008 11 12...

Страница 10: ...nditioner stops heating The air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air conditioner operates again normally The unit will not operate when it starts to de ice Fan Fan may not operate for about 3 5 minutes at the beginning to prevent any cold blasts w...

Страница 11: ...rear side panel to the right side 2 Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy then rinse it with running water and dry it in a ventilated area For best conditions repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter back in its original position...

Страница 12: ...ns repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter back in its original position The illustration shown above may differ from your depending on your model After cleaning the filter press the Filter Reset button on the remote control for 2 seconds to reset the filler schedule ...

Страница 13: ... filter 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat exchanger on the inside of the unit 2 Clean the electric components with jets of air 2 Verify that all the electric components are firmly tightened 2 Clean the fan ...

Страница 14: ...ting Anti protection of internal battery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the compressor of the outdoor unit after it has been started If the heat pump is operating in Heat mode De ice cycle is actuated to remove frost from an outdoor unit that...

Страница 15: ...fan speed does not change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the remote control after you have set the time Odors permeate in the room during operation Check if the appliance is running in a smoky area or if there is a smell entering from outside O...

Страница 16: ...off or drops on the floor HEATING 27 C or less 20 C to 24 C Internal protection triggers and the air conditioner will stop DRYING 18 C to 32 C 5 C to 43 C Condensation may occur on the indoor unit with risk to have either water blow off or drops on the floor The standardized temperature for heating is 7 C If the outdoor temperature drops to 0 C or below the heating capacity can be reduced dependin...

Страница 17: ...ust be laid and connected inside the ceiling when suspending the unit If the ceiling is already constructed lay the piping into position for connection to the unit before placing the unit inside the ceiling Note 6 Screw the nuts to suspend the unit 7 Adjust level of the unit by using measurement plate for all 4 sides For proper drainage of condensate give a 10mm 3mm slant to the left or right side...

Страница 18: ...art or hanger of pipe Add the additional insulation if the insulation plate gets thinner CAUTION Additional insulation Refrigerant pipe insulation a 3 a Hanger Drain pipe and Drain Hose Installation 1 Install the drain hose as short as possible Give a 3mm slant to the drain hose for proper drainage of condensate Secure the drain hose with the cable tie not to be separated from the unit The drain p...

Страница 19: ...of each indoor unit Refer to each installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units Coef 1 55 Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Without the drain pump 1 1 5m Horizontal dra...

Страница 20: ...dress according to the plan You may not need to set MAIN address if you selected Auto Address Setting from the outdoor unit see details on the outdoor unit installation manual Note When MAIN address is set as 12 For Example Setting RMC Address The SW03 and SW04 RMC switch is the address setting switch for controlling the indoor unit with the centralized controller You must set the SW03 SW04 and K2...

Страница 21: ...0900 SAMSUNG 0900 7267864 0 10 Min www samsung com nl NORWAY 3 SAMSUNG 7267864 www samsung com no POLAND 0 801 1SAMSUNG 172678 022 607 93 33 www samsung com pl PORTUGAL 80820 SAMSUNG 726 7864 www samsung com pt SLOVAKIA 0800 SAMSUNG 726 7864 www samsung com sk SPAIN 902 1 SAMSUNG 902 172 678 www samsung com es SWEDEN 075 SAMSUNG 726 78 64 www samsung com se U K 0845 SAMSUNG 7267864 www samsung com...