3. Check the subcooling temperature (T-subcool).
●
Calculate the degree of subcooling (T-cond _ T-subcool=subcooling Temp.)
●
If it maintains 1˚C ~ 10˚C, it is judged normal.
●
Example)
Condensing temperature (45˚C) - Subcooling temperature (42˚C) = 3˚C
●
Example)
Degree of over cooling : 1˚C
≤
3˚C
≤
10˚C
4. Check if the outdoor unit fan operates.
●
This checks the low/high operation of fan. (The operation status is displayed with red color.)