Samsung Electronics
Troubleshooting
11-34
11-4-2 Outdoor unit
1. Check the discharge temperature (T-discharge) of compressor.
●
If it maintains 70˚C ~ 110˚C, it is judged normal.
●
Example)
Discharge Temp.: 70˚C
≤
95˚C
≤
110˚C
2. Check the middle temperature of condensing temperature(T-Cond).
●
Check the middle temperature of condenser.
●
It is normal if the temperature 5˚C ~ 20˚C over than that of outdoor(T-air. out).
●
Example)
Condensing Temp.(29+5): 34˚C
≤
45˚C
≤
(29+20) : 49˚C