Troubleshooting
12-7
Samsung Electronics
12-2-6 In case of heating at the cooling mode or cooling at the heating mode
1. Troubleshooting procedure
No
No
No
Yes
Yes
Yes
OK
No
Change the setting temperature of
remote control.
Yes
Is the Thermo off?
Operate it with a heating mode
as soon as the defrosting is finished.
Yes
Is the unit
in the defrosting operation?
Turn the SW On.
No
Attach the
sensor correctly.
Over shortage
of the refrigerant
No
Yes
Yes
Is much frost
in the heat exchanger?
Is the
outdoor air sensor and
outdoor heat exchanger attached
correctly?
Connect the connecter
correctly.
No
No
Does the
4-WAY valve operate
normally?
Is the
4-WAY valve connector
connected correctly?
4-WAY valve coil error
NG
Exchange
the outdoor PCB.
4-WAY valve main body error
Go to the next page
No
Dose the
voltage of AC 220V
apply to the connector of 4-WAY
valve coil during the
operation?
After 3 minutes, cooling
and heating start automatically.
Yes
Check the resistance value
of 4-WAY valve coil.
Is the compressor
in 3 minutes off?
Indoor operation SW is on.
24437A(1)_1 1/16/05 9:58 PM Page 12-7
Содержание AS09HPB
Страница 30: ...MEMO Samsung Electronics 5 4...
Страница 34: ...MEMO Samsung Electronics 5 8...
Страница 35: ...Samsung Electronics 5 9 5 4 Ass y Control Out AS09BPAX DB93 03450B AS12BPAX DB93 03450A...
Страница 46: ...Samsung Electronics 7 2 This Document can not be used without Samsung s authorization 7 2 Outdoor Unit...
Страница 48: ...Samsung Electronics 8 2 8 2 Outdoor Unit This Document can not be used without Samsung s authorization...
Страница 80: ...MEMO 12 23 Samsung Electronics...
Страница 82: ...13 2 Samsung Electronics Block Diagram INDOOR FAN CONTROL SMPS AC COMMUNICATION SUB PCB BUZZER CONTROL...
Страница 84: ...Block Diagram 13 4 Samsung Electronics DC_LINK CAP B D DIODE IPM OUTDOOR FAN SMPS IGBT...
Страница 95: ...MEMO Samsung Electronics 14 11...