10-18
Samsung Electronics
10-2-16 DC_link voltage under/over error, H/W DC-link Over voltage protection error/PFC over load
Indoor display
3-LED DISPLAY
7-SEG DISPLAY
DESCRIPTION
LED1
LED2
LED3
E466
DC-Link voltage under/over error
E483
Over Voltage Protection Error
Outdoor display
DC-Link voltage under/over error
PFC over load
Over Voltage Protection Erro
LED ON
LED BLINKING
LED OFF
1. Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the input voltage is higher than 300Vac?
3) Is the reactor wire connected?
2. Troubleshooting procedure
YES
YES
YES
Is the connected of reactor wire?
(PBA-Reactor)
Is the the input voltage is nomal?
Normal range(180Vac ~ 270Vac)
Is the DC_link voltage
("CE101,CE102,CE103") is normal in operation mode?
Normal range(280Vdc~320Vdc)
Rest
Rest
Start the operation (cooling mode or heating mode)
NO
NO
NO
Connect the reactor wire
Check the input power in the powercord.
Check the input power
E484
PFC over load
Содержание AR18NSFHBWKNEU
Страница 11: ......
Страница 12: ......
Страница 17: ......
Страница 24: ...4 10 s c i n o r t c e l E g n u s m a S 2 2 ...
Страница 41: ...DB68 05092A 4 ...
Страница 42: ...7 2 _18K DB68 06674A 1 ...
Страница 43: ...7 3 7 2 Outdoor Unit_24K DB68 06675A DB68 06675A 00 ...
Страница 45: ...S a m s u n g C o n f i d e n t i a l S a m s u n g ...
Страница 46: ...8 3 8 3 Refrigerating Cycle Diagram ...
Страница 53: ...9 1 2 9 2 AR18NSFPEWQXEU AR24NSFPEWQXEU AR18NSFHBWKXEU AR24NSFHBWKXEU Outdoor Unit ...
Страница 90: ...10 3 10 36 ...
Страница 91: ......
Страница 92: ......
Страница 95: ...12 3 12 3 ...
Страница 96: ...12 4 12 4 ...
Страница 97: ...12 5 ...
Страница 98: ...12 6 ...
Страница 100: ...12 5 2 12 8 ...
Страница 101: ...12 6 12 9 12 6 1 12 6 2 ...
Страница 102: ...12 7 12 7 1 12 10 ...
Страница 103: ...12 7 2 12 11 ...
Страница 105: ......