※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
95
11. Installation
Important information: regulation regarding
the refrigerant used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CAUTION
•
Inform user if the system contains 5 tCO₂e or more
of fluorinated greenhouse gases. In this case, it
must be checked for leakage at least once every 12
months, according to regulation No. 517/2014. This
activity must be covered by qualified personnel
only. In the case of the situation above, the installer
(or authorized person with responsibility for final
check) must provide a maintenance book, with all
the information recorded, according to REGULATION
(EU) No. 517/2014 OF THE EUROPEAN PARLIAMENT
AND OF THE COUNCIL of 16 April 2014 on fluorinated
greenhouse gases.
1
Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product
and on this manual.
-
the factory refrigerant charge of the product,
-
the additional refrigerant amount charged in
the field and
-
+ the total refrigerant charge. on the
refrigerant charge label supplied with the
product.
Refrigerant type
GWP value
R-32
675
•
GWP: Global Warming Potential
•
Calculating tCO₂e: kg x GWP/1000
Indoor unit
Outdoor unit
Unit
Kg
tCO₂e
①
, a
②
, b
①+②
, c
NOTE
•
Factory refrigerant charge of the product: see unit
name plate
•
Additional refrigerant amount charged in the field
(Refer to the above information for the quantity of
refrigerant replenishment.)
• Total refrigerant charge
•
Refrigerant cylinder and manifold for charging
CAUTION
•
The filled-out label must be adhered in the proximity
of the product charging port (e.g. onto the inside of
the stop valve cover).
•
Make sure that the total refrigerant charge does not
exceed (A), the maximum refrigerant charge, which
is calculated in the following formula: Maximum
refrigerant charge (A)= factory refrigerant charge
(B) + maximum additional refrigerant charge due to
piping extension (C)
•
Here below, the summary table with refrigerant
charge limits for each products.
(Unit:g)
Model
A
B
C
**09TXFC***
**12TXFC***
850
700
150
**09TXCA***
**12TXCA***
1115
965
150
**24TXFC***
1525
1150
375
**18*******
**24TXEA***
1675
1300
375