Connecting the assembly cable

Connecting the cable

Electrical work 

(1)   For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the ‘wiring 

regulations’ of the Local wiring regulations.

(2) 

 

 Tighten the terminal block screw to 1.2 ~1.8 N•m (12 ~18 kgf•cm).

(3)   Precautions when connecting terminal blocks of the indoor unit

  Before connecting, make sure the connecting part of the terminal socket is facing upwards.

Upside down

The terminal 

socketis damaged.

There is no ring terminalto 

cover the wire.

  There must be no space between the terminal and the screw when connected. 

- Any remaining space may become a fire hazard due to overheating of the electrical contact.

The terminal socket 

is upside down.

Either the screw is not fitted 

properly or there is a space 

between the screw and the 

ring terminal.

•   For the terminal block wiring, use a wire with a ring terminal socket only.

 

Regular wires without a ring terminal socket may become a fire hazard due to overheating of the electrical 

contact during a wiring work.

•   Do not connect two or more different cables to extend the length. It may cause fire.

1.  Extend the assembly cable if necessary.

  When you install the unit, make first refrigerant connections and then electrical connections.  

Connect the air conditioner to grounding system before performing the electrical connection.  

If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 4.5 or 5.5 meters away from the indoor unit, you must extend the cable. The maximum length 

of the cable is 30 meters.

2 .  Open the cover panel.
3 .  Remove the screw securing the connector cover.
4 .  Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals.  

(Refer to the picture below) 

•   Each wire is labeled with the corresponding terminal number.

5 .  Pass the other end of the cable through the 65 mm hole in the wall.
6 .  Close the connector cover by tightening the screw carefully.
7 .  Close the cover panel.
8 .  Remove the terminal board cover on the side of the outdoor unit.
9.  Connect the cables to the terminals as seen in the picture.

•   Each wire is labeled with the corresponding terminal number.

English-37

In

St

All

At

IO

n

05

Содержание AR-KP/JP Series

Страница 1: ......

Страница 2: ...r commercial wastes for disposal Cool Summer Offer On those hot sweltering summer days and long restless nights there is no better escape from the heat than the cool comforts of home Your new air cond...

Страница 3: ...33 Fixing the installation plate 35 Connecting the assembly cable 36 PowerWiring and CommunicationWiring Configuration 38 Installing and connecting the assembly pipe of the indoor unit 39 Evacuating t...

Страница 4: ...k FOR INSTALLATION WARNING Use the power line with the power specifications of the product or higher and use the power line for this appliance only In addition do not use an extension line Extending t...

Страница 5: ...lt in abnormal vibrations noise or problems with the product Install the draining hose properly so that water is drained correctly Failing to do so may result in water overflowing and property damage...

Страница 6: ...se contact your nearest service center Failing to do so may result in problems with the product water leakage electric shock or fire A delivery service for the product is not provided If you reinstall...

Страница 7: ...climb onto the machine This may result in children seriously injuring themselves Do not use this air conditioner for long periods of time in badly ventilated locations or near infirm people Since this...

Страница 8: ...oduct or injury Do not operate the appliance with wet hands This may result in electric shock Do not spray volatile material such as insecticide onto the surface of the appliance As well as being harm...

Страница 9: ...loration deformation damage electric shock or fire Before cleaning or performing maintenance cut off the power supply and wait until the fan stops Failing to do so may result in electric shock or fire...

Страница 10: ...to prevent cold air when the heat pump is heating Defrost cycle The internal fan will be off to defrost ice when the heat pump is heating Vertical air flow blade will be closed during defrost cycle a...

Страница 11: ...odel Checking the name of the parts Display Air filter under the panel Airflowblade upanddown Blade pin lever Air intake Air fl ow blade left and right Room temperature sensor Remotecontrolreceiver Op...

Страница 12: ...operating modes see pages 14 15 for instructions Quiet Has no this funtion Power Turn on off the air conditioner d light Cool Has no this funtion VirusDoctor Has no this funtion Smart Saver Less ener...

Страница 13: ...ed will be displayed in the remote controller display When the icon appears change the batteries The remote controller requires two 1 5V AAA type batteries Storing the remote controller When you do no...

Страница 14: ...he temperature and the fan speed to feel cooler in hot season If current outside temperatures are much higher than the selected indoor temperature it may take time to bring the inner temperature to th...

Страница 15: ...d High Press the button to adjust the temperature Auto You can adjust the desired temperature by 1 C within the range of 16 C 30 C Cool You can adjust the desired temperature by 1 C within the range o...

Страница 16: ...he air Press the Airswing button on the remote controller again to keep the air flow direction in a constant position Make sure one of the blade pin lever that stick out of the air flow blades are not...

Страница 17: ...mote controller while the air conditioner is operating in Cool mode Smart Saver indicator and air swing indicator appears automatically on the remote controller display The air flow blades move up and...

Страница 18: ...d the Auto clean function runs Whentheairconditioneristurnedon After stopping the air conditioner operation the Auto clean indicator on the indoor unit display appears and the Auto clean function runs...

Страница 19: ...sturbed sleep if the is set too short or long because the default is set to 8 hour operation If the mode is set less than 4 hours the operation will stop at the same time If the mode is set over 5 hou...

Страница 20: ...tive it on On timer indicator stops blinking and reserved time will be displayed for 3 seconds If you don t press Set Cancel button within 10 seconds after selecting the time the air conditioner will...

Страница 21: ...eonOntimerisshorterthanOfftimer Ex On timer 3 hours Off timer 5 hours The air conditioner will operate On timer after 3 hours from the moment you have set the timer Your air conditioner will remain on...

Страница 22: ...ause it needs to be disassembled Heatexchanger Illustration may differ slightly depending on the models Make sure to turn off the power of the indoor unit and cut off the power supply before cleaning...

Страница 23: ...ilter in a ventilated area Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy rinse it with running water Clean the Air filter every 2 weeks or when the filter clean reminde...

Страница 24: ...ft it up Then pull the Air filter towards you and slide it down 3 Slide the Bio filter color in sky blue out to remove it from the slot Bio filter can be placed in any 4 slots beneath the air filter 4...

Страница 25: ...up Then pull the Air filter towards you and slide it down 3 Slide the Deodorizing filter color in black out to remove it from the slot Deodorizing filter can be placed in any 4 slots beneath the air f...

Страница 26: ...description to maintain the air conditioner properly 1 The described operations should be performed more frequently if the area of installation is very dusty 2 These operations must always be performe...

Страница 27: ...re Check if the Air filter is blocked by dirt If there is a lot of dust on the Air filter cooling heating performance may decrease Clean them frequently Check if the outdoor unit is covered or install...

Страница 28: ...ve set the time The indicator is blinking continuously Press the Power button or disconnect the power plug switch off the auxiliary power switch If the indicator is still blinking contact the service...

Страница 29: ...ccur switch the unit off and disconnect it from the power supply In order to help prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s tec...

Страница 30: ...the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to ensure the operation of any other domestic appliance connected to the same el...

Страница 31: ...aces to prevent malfunction of the unit Where there is machine oil Salty environment such as seaside areas Where sulfide gas exists Other special atmosphere areas The appearance of the unit may be dif...

Страница 32: ...0 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking front and the rear side of the outdoor unit 300 or more 1500 or more Top vi...

Страница 33: ...000 or more If installation is done in inappropriate space unit may generate sound and cause bad effect on the product Installation must be done in level and in a place where vibration will not cause...

Страница 34: ...esistance Meter Electroscope Optional accessories The following connection accessories are optional If they are not supplied you should obtain them before installing the air conditioner If these acces...

Страница 35: ...ntion to the weight of the indoor unit If you fix the indoor unit on a window frame 1 Determine the positions of the wooden uprights to be attached to the window frame 2 Attach the wooden uprights to...

Страница 36: ...LEC H07RN F IEC 60245 IEC 57 CENELEC H05RN F Model Powercable Interconnectioncable TypeGL 30 3G4 0mm H07RN F 3Gx2 5mm H07RN F 1x0 75mm H05RN F 25A This equipment complies with IEC 61000 3 12 provided...

Страница 37: ...contact during a wiring work Do not connect two or more different cables to extend the length It may cause fire 1 Extend the assembly cable if necessary When you install the unit make first refrigera...

Страница 38: ...power cable and the main power cable in the cable tube Secure the cable tube to the outdoor knockout using the CD connector and bushing Arrange the cables as shown in the picture The diameter of the 6...

Страница 39: ...optional The connection procedure for the refrigerant pipe varies according to the exit position of the pipe when facing the wall Right A Left B Underside C Rear Outer Diameter Torque N m kgf cm 6 35...

Страница 40: ...1 Unscrew the caps at the end of each pipe All inert gas exhausts from the indoor unit The indoor unit is supplied with inert gas nitrogen Before installing the unit check if nitrogen gas flow out of...

Страница 41: ...ding brazing please ensure nitrogen is used during welding brazing process The joint must be accessible and serviceable Tighten the flare nut with torque wrench according to specified method If the fl...

Страница 42: ...e is no water leakage 5 Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose Then Use vinyl tape to wrap the each side of connection by 20 mm If you do not use the other drain...

Страница 43: ...gh the hole in the wall Check if it slants downwards as seen in the picture 8 Using natural drainage method check the drainage is normal Shield Drain hose Extension drain hose Installingandconnectingt...

Страница 44: ...w could block the air intake To avoid this incident install a frame that is higher than estimated snow fall In addition install a snow proof hood to avoid snow from piling on the outdoor unit When ins...

Страница 45: ...to avoid a gas leak Close the valve of the low pressure side of manifold gauge clockwise Turn off the vacuum pump Check for 2 minutes if there is any pressure change Remove the hose of the low pressur...

Страница 46: ...ng core Spindle R 22 Diameter of the screw 7 16 20UNF R 410A Diameter of the screw 1 2 20UNF Tightening torque for charging port cap Refer to the table Test part for indoor unit Before inspecting the...

Страница 47: ...g winds or at a height fix it to an appropriate support wall or ground 1 Place the outdoor unit as indicated on the top of the unit to let the discharged air out properly 2 Fix the outdoor unit in lev...

Страница 48: ...set the temperature at 16 C In Heat mode use Temp or button and set the temperature at 30 C Cooling mode indoor unit check Inlet air temp Outlet air temp From 10 K to 12 K indicative deltaT Heating mo...

Страница 49: ...ork is completed wrap it with the insulation tape to finish Tools Crimping pliers Connectionsleeve mm Insulation tape Contractiontube mm Spec MH 14 20x 7 0 HxOD Width 18 mm 50x 8 0 LxOD Shape 40 mm In...

Страница 50: ...OOLING 2945W 3380W HEATING H1 EER COP COOLING 9 51 Btu h W 7 25 Btu h W HEATING H1 REFRIGERANT TYPE R 22 CHARGE 1270 g 44 80 oz ANNUAL ENERGY CONSUMPTION 7952 kWh Year TEMPERATURE INDOOR 27 C 29 C 19...

Страница 51: ...678 www samsung com pk support TUNISIA 80 1000 12 www samsung com n_africa support U A E 800 SAMSUNG 800 726 7864 www samsung com ae support English www samsung com ae_ar support Arabic OMAN 800 SAMSU...

Страница 52: ...AR KP JP Series AR KC JC Series AS32U Series Air Conditioner user installation manual imagine the possibilities Thank you for purchasing this Samsung product DB68 06393A 00 EN FR AR...

Отзывы: