Connecting the assembly cable
Cable specification
• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it
must be incorporated in a wire with a contact opening of ≥3 mm.
• Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.
• Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC: 60245 IEC 66/CENELEC: H07RN-F, IEC: 60245 IEC 57/CENELEC: H05RN-F)
Model
Power cable
Interconnection cable
Type GL
30
3G4.0mm² H07RN-F
3Gx2.5mm² H07RN-F
1x0.75mm² H05RN-F
25A
•
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal
to Ssc(*2) at the interface point between the user’s supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Model
Ssc[MvA]
AR30KCFUDUQ/QT
0 .098 (T1) / 0 .113 (T3)
English-36