Air conditioner

Installation manual

AR



HS/JS



 

Thank you for purchasing this Samsung air conditioner.

 

Before operating this unit, please read this Installation manual carefully and retain it for future 
reference.

A3050_EU_Best model_IM_DB68-06152A-00_EN.indd   32

2016/4/20   14:10:13

Содержание AR**HS

Страница 1: ...Air Insta AR H Thank yo Before op reference A3050_EU_Best model_IM_DB68 06152A 00_EN indd 32 2016 4 20 14 10 13 ...

Страница 2: ...AR HS JS Thank you for purchasing this Samsung air conditioner Before operating this unit please read this Installation manual carefully and retain it for future reference A3050_EU_Best model_IM_DB68 06152A 00_EN indd 1 2016 4 20 14 10 13 ...

Страница 3: ... Step 2 9 Shortening or extending the refrigerant pipes assembly pipe Step 2 10 Fixing the installation plate Step 2 11 Fixing the indoor unit to the installation plate Step 2 12 Assembling the cover panel Outdoor Unit Installation 17 Step 3 1 Fixing the outdoor unit in place Step 3 2 Connecting the power and communication cables and the refrigerant pipes Step 3 3 Evacuating the air Step 3 4 Addin...

Страница 4: ...be performed by qualified personnel only The unit contains moving parts which should always be kept out of the reach of children Do not attempt to repair move alter or reinstall the unit If performed by unauthorised personnel these operations may cause electric shocks or fires Do not place containers with liquids or other objects on the unit All the materials used for the manufacture and packaging...

Страница 5: ... sea water and the dust on the heat exchanger of the outdoor unit and apply a corrosion inhibitor on it At least once in a year Power supply line fuse or circuit breaker Always make sure that the power supply is compliant with current safety standards Always install the air conditioner in compliance with current local safety standards Always verify that a suitable grounding connection is available...

Страница 6: ...m Model Pipe length Pipe height Minimum Maximum Maximum 09 12 3 15 8 100 mm or more 125 mm or more 125 mm or more Drain hose hole You can select the direction of draining left or right Maximum pipe height 8 m Maximum pipe length 15 m Make at least one round to reduce noise and vibration The actual units may look different from the images depicted here Make a U trap A on the pipe which is connected...

Страница 7: ...ole product Be sure to install the outdoor unit in a level place where its vibration does not affect the whole product Step 1 2 Checking and preparing accessories and tools Accessories Accessories in the indoor unit package Installation plate 1 Remote control 1 Remote control battery 2 User Manual 1 Installation Manual 1 Smart A C application Manual 1 Cap screw 2 Guide Left 1 Guide Right 1 Case Su...

Страница 8: ...pipes If these accessories are supplied they are in the accessory package or outdoor unit package Tools General tools Vacuum pump Backward flowing prevention Manifold gauge Stud finder Torque wrench Pipe cutter Reamer Pipe bender Spirit level Screwdriver Spanner Drill L wrench Measuring tape Tools for test operation Thermometer Resistance meter Electroscope Step 1 3 Drilling a hole through the wal...

Страница 9: ...efrigerant pipes as shown in the figure This wrapping minimises condensation problem 2 Wind the refrigerant pipes power cable communication cable and drain hose with vinyl tape to make a pipe bundle Possible directions of the pipe bundle Left Right Rear right or left Bottom right Wall Drain hose Indoor unit The hole slants downwards Insulation Refrigerant pipes Refrigerant pipes assembly pipe Inst...

Страница 10: ...e bottom hooks to pull out the cover panel B B C A A 1 2 4 Step 2 2 Disassembling the installation plate Indoor Unit Installation Please scan this QR code for detail video of indoor unit installation Cap screw Phillips screwdriver Screw Flat head screwdriver Centre hook A Bottom Side hook B C A3050_EU_Best model_IM_DB68 06152A 00_EN indd 9 2016 4 20 14 10 18 ...

Страница 11: ...ay become a hazard due to overheating of the electrical contact during installation If you need to extend the pipe be sure to extend the cable too The maximum length of each of the cable and pipe used should not exceed 15 metres Do not connect two or more different cables to extend the length This connection may cause fire Each circular terminal must match the size of its corresponding screw in th...

Страница 12: ...s in the same location The compression dimension should be 8 0 After compressing it pull both sides of the wire to make sure it is firmly pressed 5 Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape A total of three or more layers of insulation is required 6 Apply heat to the contraction tube to contract it 7 After tube contractio...

Страница 13: ...han the product s drain hose water leakage may occur Inadequate installation may cause water leakage If the drain hose is routed inside the room insulate the hose so that dripping condensation does not damage the furniture or floors Do not box in or cover the drain hose connection Drain hose connection must be easily accessible and serviceable Step 2 6 Optional Extending the drain hose A B Drain h...

Страница 14: ...cumstances must sanitary type copper pipe be used There are 2 refrigerant pipes of different diameters The smaller one is for the liquid refrigerant The larger one is for the gas refrigerant A short liquid refrigerant pipe and a short gas refrigerant pipe are already fitted to the air conditioner The connection procedure for the refrigerant pipes varies according to the exit position of each pipe ...

Страница 15: ...ndoor unit as shown in the picture 2 9 Assemble the Guide into the position of A or B as shown in the picture 3 NOTE The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test For further details see Step 4 1 Performing the gas leak tests on page 21 CAUTION Tighten the flare nut with a torque wrench according to specified method If the fla...

Страница 16: ...stand the weight of the indoor unit If you install the indoor unit in a place where it is not strong enough to withstand the unit s weight the unit could fall and cause injury When fixing the indoor unit on a wall Fix the installation plate to the wall giving attention to the weight of the indoor unit B A D C NOTE If you mount the plate to a concrete wall using plastic anchors make sure that gaps ...

Страница 17: ... injury or equipment damage Search for other spots if there are less than two studs or the distance between the studs are different from the plate hanger Fix the installation plate without inclining to one side Step 2 11 Fixing the indoor unit to the installation plate CAUTION Make sure that the pipe bundle does not move when you install the indoor unit onto the installation plate Step 2 12 Assemb...

Страница 18: ...e sure that the wall can support the weights of the rack and the outdoor unit Install the rack close to the column as much as possible Step 3 2 Connecting the power and communication cables and the refrigerant pipes F1 F2 L N CAUTION Be sure to fix the power cables and communication cable with a cable clamp Power Communication cable shall not exceed 30m Outdoor Unit Installation Unit mm Model X Y ...

Страница 19: ...N position of Electronic Expansion Valve 2 Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture 3 4 5 3 Open the valve of the low pressure side of manifold gauge anticlockwise 4 Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes Make sure that pressure gauge shows 0 1 MPa 76 cmHg 5 torr after about 10 minu...

Страница 20: ... regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere CAUTION Inform user if system contains 5 tCO2 e or more of fluorinated greenhouse gases In this case it has to be checked for leakage at least once every 12 months according to regulation n 517 2014 This activity has to be covered by qualified personnel only In case situation ab...

Страница 21: ...r to the above information for the quantity of refrigerant replenishment C Total refrigerant charge d Refrigerant cylinder and manifold for charging CAUTION The filled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover A3050_EU_Best model_IM_DB68 06152A 00_EN indd 20 2016 4 20 14 10 24 ...

Страница 22: ...as a number between 0 and 99 on the indoor unit display The LEDs on the indoor unit display blink in sequence then all of them blink simultaneously These operations repeat When Smart Install mode succeeds Smart Install mode ends with ringing sound and the air conditioner is in standby status When Smart Install mode fails An error message is displayed on the indoor unit display and Smart Install mo...

Страница 23: ... connector Error on indoor fan motor Check the connection of the connector Remove foreign substance Check for the cause that restrains motor display and all LEDs blink EEPROM Option error Re set options Refrigerant flow blocking error Check if the stop valve is completely open Check if there is any blockage in the refrigerant pipe which connects the indoor and outdoor units Check for refrigerant l...

Страница 24: ...door unit This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere 1 Shut off the liquid valve with the Allen wrench 2 Turn on the air conditioner in cooling with fan operating at high velocity Compressor will immediately start provided 3 minutes have elapsed since the last stop 3 After 2 minutes of operation shut the sucti...

Страница 25: ...b PCB as seen in the picture 5 Connect the wire remote controller central remote controller etc to the Sub PCB 6 Assemble the Cover PCB and the front panel If the Sub PCB is not installed arrange the wire for multi system connection as shown in the illustration NOTE The Sub PCB is attached to be controlled by the wired remote controller and central controller Sub PCB installation optional Wire for...