background image

WWW.SUNLIGHTSUPPLY.COM

Distributed by:

BASIC TECHNICAL INFORMATION FOR: 

SAMSUNG MAX

MINI-SPLIT UNITS

Содержание AQN12VFUAGM

Страница 1: ...WWW SUNLIGHTSUPPLY COM Distributed by BASIC TECHNICAL INFORMATION FOR SAMSUNG MAX MINI SPLIT UNITS ...

Страница 2: ... 0 16 oz ft over 25 ft CHARGE FOR LINE RUN LENGTHS Length 25 35 45 50 Added Charge oz 0 1 6 3 3 4 0 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconnecting Wires 3x14 AWG Power 2x16 AWG Control 5 Total LINE SIZES Liquid expanded gas line 1 4 Suction 3 8 BOTH LINES MUST BE INSULATED SEPARATELY Samsung MAX 12 000 BTU Mini Split Indoor Unit 700550 AQN12VFUAGM...

Страница 3: ...FOR LINE RUN LENGTHS Length 25 35 45 55 65 75 85 95 98 Added Charge oz 0 1 6 3 2 4 8 6 4 8 0 9 6 11 2 11 68 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconnecting Wires 3x14 AWG Power 2x16 AWG Control 5 Total LINE SIZES Liquid expanded gas line 1 4 Suction 5 8 BOTH LINES MUST BE INSULATED SEPARATELY Samsung MAX 24 000 BTU Mini Split Indoor Unit 700554 AQN...

Страница 4: ... LINE RUN LENGTHS Length 25 35 45 55 65 75 85 95 98 Added Charge oz 0 4 3 8 6 12 9 17 2 21 5 25 8 30 1 32 25 INTERCONNECTING WIRING Gauge 14 AWG Power 16 AWG Shielded Communication Number of Interconnecting Wires 3x14 AWG Power 2x16 AWG Control 5 Total LINE SIZES Liquid expanded gas line 1 4 Suction 5 8 BOTH LINES MUST BE INSULATED SEPARATELY Samsung MAX 36 000 BTU Mini Split Indoor Unit 700558 AQ...

Страница 5: ...equired to control MAX models with Samsung central control options upper level control Includes sub PCB 4 crimp wire connectors wire harness and sub PCB cover sub PCB Wire Harness sub PCB 1 With the power off open the front panel of the MAX indoor unit Remove the main PCB cover by removing the screw in the bottom corner Make sure the power is turned off to the outdoor unit before opening the indoo...

Страница 6: ...ently pull this wire upward and out of the unit 3 Connect the PCB to the PCB wire harness a and to the sub PCB wire harness b NOTE the sub PCB wire harness is included with the wired controller a b 4 Remove the protective tape a and slide all connected wires into the groove beside the sub PCB mounting location b Snap the sub PCB cover over the installed sub PCB a b c ...

Страница 7: ...ired controller wires already installed pull the wires through the front of the indoor unit Cut the 2 small plastic connectors off the ends of the sub PCB wire harness the ends of the red blue and yellow orange wires Connect F3 F4 and V1 V2 between the indoor unit and the wired controller as pictured below RED F3 BLUE F4 ORANGE V1 YELLOW V2 Remove Wired controller wire field provided PCB wire harn...

Страница 8: ...E CAN BE EXPECTED DOWN TO 0ºF OUTDOOR TEMPERATURE PLEASE NOTE THAT IF A PROLONGED OFF CYCLE IS EXPERIENCED IN OUTDOOR TEMPERATURES BELOW 10ºF THE UNIT MAY NOT RESTART UNTIL THE TEMPERATURE RISES ABOVE 14ºF R410A REFRIGERANT Higher pressures close to double than R22 but the operating temperatures are very similar to those with R22 For example A saturated suction temperature of 45ºF Suction Pressure...

Страница 9: ...e an adverse affect on the system s ability to properly return oil to the compressor Over time this will cause inconsistent performance error codes and premature failure of components Ceiling Cassette units must have a Minimum Distance of 5ft from the louver opening to any wall or other obstacle for the same reasons as listed above Ensure line set runs are adhered to it is required that a minimum ...

Страница 10: ...Distributed by ...

Отзывы: