E-
7
ENGLISH
When using NFB (No Fuse Breaker)
❈
The outdoor unit circuit is shipped based on the NFB power source wiring.
1. Remove the cover of electric box on side panel of the outdoor unit.
2. Connect the electric input wires (R,S,T,N) to each terminal (R,S,T,N) of the electric box on the outdoor unit
respectively. (Input wires are purchased by the user separately.)
3. Connect the electric wires to each terminal on the indoor and outdoor unit respectively.
❏
When connecting 3Phase 4wires 380V AC
OUTDOOR SIDE
Power terminals on the outdoor unit
Connector
Blue
Brown
Blue
Brown
Knife switch or
automatic circuit
breaker
NFB
Electric input wires
Indoor / outdoor unit
connecting wire
Wire of sensor
A
APV48QOAN_E_IM_00000 2008.10.20 11:5 PM Page 7