When there is tall obstacle around the outdoor unit
X
f
If the obstacle in the front side of the outdoor unit exceeds
1500mm, half of the exceeding height (h1/2) must be added to the
space in front of the outdoor unit (S1).
X
f
If the obstacle in front of the air inlet side exceeds 50mm, half of the
exceeding height (h2/2) must be added to the space in the air inlet
side (S2).
(Unit: mm)
Fr
on
t side
1500
500
h1
h2
S1+h1/2
S2+h2/2
Air inlet
Outdoor
unit
AP0AS0
✴
X
❖
When there are no tall obstacles around the outdoor unit
Wall height restricted
Wall height unrestricted
❋
When installing 1 outdoor unit
(Unit: mm)
<Case 1>
300 or
mor
e
500 or mor
e
10 or more
200 or
more
Front
<Case 2>
50 or more
50 or
more
Front
100 or mor
e
500 or mor
e
<Case 3>
200 or
more
The height of the
wall is unlimited
300 or mor
e
Pipe length between the indoor and the outdoor unit
X
f
If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the pipe
length should be as short as possible.
- Allowable pipe length: Maximum 50m
- Allowable pipe height difference:
When outdoor unit is installed higher level than indoor unit: Maximum 30m
When indoor unit is installed higher level than indoor unit: Maximum 20m
X
f
Choose a installation place where you can limit the pipe bending to less than 10.
Less than 20m
Indoor
unit
Indoor
unit
Outdoor
unit
Outdoor
unit
Less than 30m