29
English
Instal
lation Pr
oc
edur
e
02 series installation option (Detailed)
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Evaporator Drying
Use of external room temperature sensor /
Minimizing fan operation when thermostat is off
Use of central
control
FAN RPM compensation
Indication
and Details
Indication Details Indication Details Indication
Details
Indication
Details
Indication Details Indication
Details
Use of
External room
temperature
sensor
Minimizing fan
operation when
thermostat is off
0
2
0
Disuse
0
Default
Default
0
Disuse
0
Disuse
1
Use
Disuse
2
Disuse
Use (Heating) (*2)
2
Use (5min) (*1)
3
Use
Use (Heating) (*2)
4
Disuse
Use (Cooling) (*2)
1
RPM
compensation
5
Use
Use (Cooling) (*2)
4
Use (10min) (*1)
6
Disuse
Use (Heating /
Cooling) (*2)
1
Use
7
Use
Use (Heating /
Cooling) (*2)
8
Disuse
Use (Cooling Ultra
Low Fan ) (*2)
2
High ceiling
KIT (4way
model only)
6
Use (30min) (*1)
9
Use
Use (Cooling Ultra
Low Fan ) (*2)
A
Disuse
Use (Heating / Cooling
Ultra Low Fan ) (*2)
B
Use
Use (Heating / Cooling
Ultra Low Fan ) (*2)
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Use of drain pump
Use of hot water heater
EEV Step when
heating stops
Dew removal operation in
wind free mode
Indication
and Details
Indication Details Indication Details Indication
Details
Indication Details Indication
Details
1
0
Disuse
0
Disuse
0
Default
0
(Default)
Maintain
blade status
in wind free
mode
1
Use
1
Use (*3)
1
Adjusted
EEV Step
setting
1
Cooling
operation by
opening the
blade
2
When an
indoor unit
stops, drain
pump will
operate for
3min
3
Use (*3)
DVM TK Wind-Free 1way IM EN_DB68-07553A-00.indb 29
2017-12-01 오후 2:19:09