(*3)
Heater operation when the SeG9 of 02 series installation option is set to using hot water heater or when SeG15 is set to
using external heater
e.g. 1) Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: Hot water heater is turned on at the same time as the
heating thermostat is on, and turned off when the heating thermostat is off .
e.g. 2) Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”:
Room temp . ≤ set temp . + f(heating compensation temp .)
- external heater is turned on when the temperature is maintained as 4 .5 °C for 10 minutes .
Room temp . > set temp . + f(heating compensation temp .)
- external heater is turned off when the temperature is maintained as 4 .5 °C + 1 °C (1 °C is the Hysteresis for On/
Off selection .]
Additional information on SeG 3, 4, 5, 6, 8, 9
When the SeG 3 is set as “1” and follow AutoChangeOver for HR only operation, it will operate as below .
A : Set with SeG4(˚C)
B : Set with SeG5(˚C)
C : Set with SeG6(˚C)
D : Set with SeG8(˚C)
Cooling T
hermo
O
ff
Hea
ting T
hermo
O
ff
Cooling T
hermo
O
n
Hea
ting T
hermo
O
n
B
C
D
Ts
A
c
a
Temp .
d
b
Standard temp . for Heating
Standard temp . for Cooling
Standard temp . for
Heating
Cooling
Standard temp . for
Cooling
Heating
Set temp . for Auto mode
❋
❋
Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SeG9 .
ENGLISH-31